Proline t-mass A 150 HART
Commissioning
Hauser
51
10.4.4 Configuring the current output
Navigation path
"Setup" menu →Assign current output
"Setup" menu →4mA value
"Setup" menu →20mA value
Parameter overview with brief description
Parameter
Description
Selection/
User entry
Factory setting
Assign current output
Use this function to assign a
measured variable or process
variable to the current output
Mass flow
Corrected volume flow
FAD volume flow
Temperature
Mass flow
4mA value
Enter the value for the 4 mA
current. The value can be larger
than or smaller than the 20 mA
value assigned. Positive and
negative values are permitted
depending on the measured
variable (e.g. mass flow)
assigned.
Number with up to 3
decimal places from - to
+. The unit depends on
the measured variable
assigned.
0
20mA value
Enter the value for the 20 mA
current. The value can be larger
than or smaller than the 4 mA
value assigned. Positive and
negative values are permitted
depending on the measured
variable (e.g. mass flow)
assigned.
Number with up to 3
decimal places from - to
+. The unit depends on
the measured variable
assigned.
Maximum calibrated
full scale value
10.4.5 Configuring the pulse/frequency/switch output
Navigation path
• "Setup" menu →Operating mode
• "Setup" menu →Assign frequency output
• "Setup" menu →Switch output function
• "Setup" menu →Assign pulse output
Parameter overview with brief description
Parameter
Description
Selection/
User entry
Factory setting
Operating mode
Specify the output as a
pulse, frequency or switch
output.
• Pulse
• Frequency
• Switch
Pulse
Assign frequency output
Select the process variable
for the frequency output.
• Off
• Mass flow
• Corrected volume flow
• FAD volume flow
• Temperature
Off
Measuring value at
minimum frequency
Enter the measured value
at the minimum
frequency.
Depends on the process
variable selected
-