Proline t-mass A 150 HART
Technical data
Hauser
103
‣
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
Storage temperature
–40 to +80 °C (–40 to +176 °F), preferably at +20 °C (+68 °F)
Degree of protection
Transmitter
• As standard: IP66/67, type 4X enclosure
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure
Sensor
IP66/67, type 4X enclosure
Shock resistance
As per IEC/EN 60068-2-31
Vibration resistance
Acceleration up to 2 g, 10 to 150 Hz, as per IEC/EN 60068-2-6
Electromagnetic
compatibility (EMC)
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21).
For details, refer to the Declaration of Conformity.
17.9 Process
Medium temperature range
Sensor
• Flange and threaded connection made of stainless steel:
–40 to +100 °C (–40 to +212 °F)
• Flange connection PN16 made of carbon steel:
–10 to +100 °C (–14 to +212 °F)
• Flange connection Cl.150 made of carbon steel:
–29 to +100 °C (–20.2 to +212 °F)
Flow limit
See "Measuring range"→ 95 section
The velocity in the measuring tube should not exceed 70 m/s (230 ft/s).
Pressure loss
Negligible (without flow conditioner).
For a precise calculation, use the Applicator.
System pressure
Sensor
Depending on the version, please note the details on the name plate .
Max. 40 bar g (580 psi g)
Thermal insulation
If the gas is very humid or saturated with water, the pipe and the sensor housing should be
insulated to prevent water droplets condensing on the transducer.
NOTICE
Electronics overheating on account of thermal insulation!
‣
Observe maximum permitted insulation height of the transmitter neck so that the
transmitter head is completely free.