Commissioning
Proline t-mass 65 PROFIBUS DP/PA
72
Hauser
7.6.4
Configuration examples with Simatic S7 HW-Konfig
Example 1
A0005497
Fig. 39: Complete
configuration using the t-mass 65 GSD file
It is essential to adhere to the following sequence when configuring the modules in the
PROFIBUS Master (class 1):
Slot
sequence
(Slot)
Module
Byte length
input data
Byte length
output data
Description
1
AI
5
-
Analog Input function block 1
Output variable
Mass flow (factory set-
ting)
2
AI
5
-
Analog Input function block 1
Output variable
Corrected volume flow
(factory setting)
3
AI
5
-
Analog Input function block 1
Output variable
Temperature (factory set-
ting)
4
SETTOT
_MODETOT
_TOTAL
5
2
Totalizer function block 1
TOTAL
output variable = totalized mass
flow (factory setting)
SETTOT
totalizer control
MODETOT
totalizer configuration
5
SETTOT
_MODETOT
_TOTAL
5
2
Totalizer function block 2
TOTAL
output variable = totalized mass
flow (factory setting)
SETTOT
totalizer control
MODETOT
totalizer configuration
6
DISPLAY_VALUE
-
5
Value for local display
7
CONTROL_BLOCK
-
1
Control of device functions
8
PRESSURE_VALUE
-
5
Process pressure
9
FRACTION_INPUT
-
5
Analyzer input