Operation with touch control

Display elements

• 4-line, illuminated, graphic display

• White background lighting; switches to red in event of device errors

• Format for displaying measured variables and status variables can be individually configured

• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)

The readability of the display may be impaired at temperatures outside the temperature range.

Operating elements

• External operation via touch control (3 optical keys) without opening the housing: , , 

• Operating elements also accessible in various hazardous areas

Via remote display and operating module DKX001

The remote display and operating module DKX001 is available as an optional extra:

Order code for "Display; operation", option 

O

 "Separate backlit, 4-line display; 10 m (30 ft) Cable;

touch control"

Another device version, e.g. other housing material, other cable length etc., can be ordered via

the separate product structure DKX001. The measuring device is ordered with:

Order code for "Display; operation", option 

M

 "None, prepared for remote display"

  A0026786

 31

Operation via remote display and operating module DKX001

Display and operating elements

The display and operating elements correspond to those of the display module .

• The measuring device is always supplied with a dummy cover when the remote display and

operating module DKX001 is used. Display or operation at the transmitter is not possible in

this case.

• The remote display and operating module DKX001 can also be ordered separately and

subsequently as an accessory without a measuring device →   81.

• If ordered subsequently: The remote display and operating module DKX001 cannot be

connected at the same time as the existing display or operation unit. Only one display or

operation unit may be connected to the transmitter at any one time.

Summary of Contents for Proline Promass Q 300

Page 1: ...ay with touch control and WLAN access Remote display available Your benefits Guaranteed measurement quality premium accuracy for mass flow volume flow and density Optimized performance for liquids wit...

Page 2: ...on 40 Inlet and outlet runs 41 Special mounting instructions 41 Environment 43 Ambient temperature range 43 Storage temperature 43 Climate class 43 Degree of protection 43 Vibration resistance 43 Shoc...

Page 3: ...Technology 80 Concentration 81 Accessories 81 Device specific accessories 81 Communication specific accessories 82 Service specific accessories 82 System components 83 Supplementary documentation 83 S...

Page 4: ...ation line or a star grounding system depending on national or company codes of practice Communication symbols Symbol Meaning Wireless Local Area Network WLAN Communication via a wireless local networ...

Page 5: ...n the mass flow Instead of a constant rotational velocity the sensor uses oscillation In the sensor two parallel measuring tubes containing flowing fluid oscillate in antiphase acting like a tuning fo...

Page 6: ...vailable as a compact version The transmitter and sensor form a mechanical unit Transmitter Promass 300 A0026708 Device versions and materials Transmitter housing Aluminum coated aluminum AlSi10Mg coa...

Page 7: ...w of the most important functions is provided in the following section Protecting access via hardware write protection Write access to the device parameters via the local display Web browser or operat...

Page 8: ...ible for the management and careful handling of the access code and network key Access via fieldbus When communicating via fieldbus access to the device parameters can be restricted to Read only acces...

Page 9: ...or gases The full scale values depend on the density of the gas and can be calculated with the formula below max G max F G x max G Maximum full scale value for gas kg h max F Maximum full scale value...

Page 10: ...n system to the measuring device via the HART protocol The pressure transmitter must support the following protocol specific functions HART protocol Burst mode Current input The measured values are wr...

Page 11: ...ne Promass Q 300 Endress Hauser 11 Input signal level Low signal DC 3 to 5 V High signal DC 12 to 30 V Assignable functions Off Reset the individual totalizers separately Reset all totalizers Flow ove...

Page 12: ...MA Order code for Output input 2 021 Not assigned A A A A A A A Current output 0 4 to 20 mA B B B B Current output 0 4 to 20 mA Ex i C C C User configurable input output 1 D D D D Pulse frequency swi...

Page 13: ...58 2 MBP galvanically isolated Data transfer 31 25 KBit s Current consumption 10 mA Permitted supply voltage 9 to 32 V Bus connection With integrated reverse polarity protection FOUNDATION Fieldbus FO...

Page 14: ...ve Maximum output current 22 5 mA active Open circuit voltage DC 28 8 V active Pulse width Adjustable 0 05 to 2000 ms Maximum pulse rate 10000 Impulse s Pulse value Adjustable Assignable measured vari...

Page 15: ...s one or more application packages Double pulse output Function Double pulse Version Open collector Can be set to Active Passive Maximum input values DC 30 V 250 mA passive Open circuit voltage DC 28...

Page 16: ...for assignment Choice of current output 4 to 20 mA active 0 4 to 20 mA passive Pulse frequency switch output Choice of current input 4 to 20 mA active 0 4 to 20 mA passive Status input The technical v...

Page 17: ...equency switch output Pulse output Failure mode Choose from Actual value No pulses Frequency output Failure mode Choose from Actual value 0 Hz Defined value f max 2 to 12500 Hz Switch output Failure m...

Page 18: ...Safety related values Output input 1 26 27 Option BA Current output 4 to 20 mA HART Unom 30 V Umax 250 V Option GA PROFIBUS PA Unom 32 V Umax 250 V Option MA Modbus RS485 Unom 30 V Umax 250 V Option...

Page 19: ...lass I Division 1 version 2 Only available for the Zone 2 Class I Division 2 version transmitter Order code for Output input 2 Output input 3 Output type Intrinsically safe values Intrinsically safe v...

Page 20: ...device has one or more application packages Heartbeat Technology Application Package Additional measured variables are available with the Heartbeat Technology application package Oscillation amplitud...

Page 21: ...olume flow Corrected volume flow Target mass flow Carrier mass flow Input values from automation system to measuring device Analog output 1 to 3 fixed assignment Analog output 1 external pressure Anal...

Page 22: ...of the function scope of compatibility Operating Instructions 84 FOUNDATION Fieldbus Manufacturer ID 0x452B48 Ident number 0x103B Device revision 1 DD revision Information and files under www endress...

Page 23: ...tion Transducer Block TRDEXPIN Parameters that provide information about the state of the device No output values Service Sensor Transducer Block TRDSRVS Parameters that can only be accessed by Endres...

Page 24: ...ow flow cut off 103 Empty pipe detection 104 Status verification 105 PID Block PID 1 6 ms Multiple Analog Output Block MAO 1 5 ms Channel_0 121 Value 1 External compensation variable pressure Value 2...

Page 25: ...ed the Promass 300 measuring device supports the compatibility of the Modbus registers for process variables and diagnostic information with the earlier Promass 83 model It is not necessary to change...

Page 26: ...de for Input output 1 option GA PROFIBUS PA Order code for Electrical connection Cable entry 2 Cable entry 3 L N P U Plug M12 1 Order code for Input output 1 option SA FOUNDATION Fieldbus Order code f...

Page 27: ...ting the transmitter Terminal assignment 25 Device plugs available 26 1 2 3 A0026781 1 Cable entry for supply voltage 2 Cable entry for input output signal transmission 3 Cable entry for input output...

Page 28: ...e cable specifications 34 3 Connection for HART operating devices 70 4 Resistor for HART communication 250 observe maximum load 13 5 Analog display unit observe maximum load 13 6 Transmitter 2 3 4 20...

Page 29: ...EMC requirements observe cable specifications 4 Analog display unit observe maximum load 5 Pressure transmitter e g Cerabar M Cerabar S see requirements 6 Transmitter PROFIBUS PA 2 1 3 4 7 8 6 6 6 6 5...

Page 30: ...both ends to comply with EMC requirements observe cable specifications 4 T box 5 Measuring device 6 Local grounding 7 Bus terminator 8 Potential matching line Modbus RS485 2 1 A B 3 4 4 A B A B A0028...

Page 31: ...er 2 4 20 mA 3 1 4 A0028759 9 Connection example for 4 20 mA current output passive 1 Automation system with current input e g PLC 2 Active barrier for power supply e g RN221N 3 Analog display unit ob...

Page 32: ...0 12 Connection example for double pulse output active 1 Automation system with double pulse input e g PLC 2 Transmitter Observe input values 15 3 Double pulse output 4 Double pulse output slave phase...

Page 33: ...put 1 Power supply 2 External measuring device for reading in pressure or temperature for instance 3 Transmitter Observe input values Status input 1 2 3 A0028764 16 Connection example for status input...

Page 34: ...planning and commissioning BA00034S PNO Directive 2 092 PROFIBUS PA User and Installation Guideline IEC 61158 2 MBP FOUNDATION Fieldbus Twisted shielded two wire cable For further information on plann...

Page 35: ...1 Class I Division 1 L R Maximum 24 H for Zone 1 Class I Division 1 Cable length Maximum 300 m 1000 ft see the following table Cross section Cable length for use in non hazardous area Ex Zone 2 Class...

Page 36: ...Density liquids 0 2 kg m 0 0002 g cm Valid between 20 C and 60 C The measured error increases by 0 015 kg m3 C outside the temperature range Valid range for density calibration 0 to 2000 kg m 20 to 6...

Page 37: ...racy specifications Current output Accuracy 5 A Pulse frequency output o r of reading Accuracy Max 50 ppm o r across the entire ambient temperature range Repeatability o r of reading 1 g cm3 1 kg l T...

Page 38: ...density calibration temperature and the process temperature the typical measured error of the sensor is 0 015 kg m3 C 0 0075 kg m3 F kg m 3 0 0 5 1 0 1 5 2 0 2 5 3 0 C F 200 150 100 50 0 50 100 150 2...

Page 39: ...00 A0021332 BaseAccu A0021339 ZeroPoint BaseAccu 100 A0021333 ZeroPoint MeasValue 100 A0021334 Calculation of the maximum repeatability as a function of the flow rate Flow rate Maximum repeatability i...

Page 40: ...al pipeline Pipe restrictions or the use of an orifice with a smaller cross section than the nominal diameter prevent the sensor running empty while measurement is in progress 1 2 3 4 5 A0028773 17 In...

Page 41: ...rved measuring tube 1 Avoid this orientation for fluids with entrained solids Risk of solids accumulating 2 Avoid this orientation for outgassing fluids Risk of gas accumulating Inlet and outlet runs...

Page 42: ...erence conditions 36 Therefore a zero point adjustment in the field is generally not required Experience shows that zero point adjustment is advisable only in special cases To achieve maximum measurin...

Page 43: ...ather protection cover from Endress Hauser 81 Storage temperature 50 to 80 C 58 to 176 F Climate class DIN EN 60068 2 38 test Z AD Degree of protection Transmitter and sensor As standard IP66 67 type...

Page 44: ...to 205 C 58 to 401 F Low temperature 196 to 150 C 320 to 302 F Order code for Measuring tube material option LA TA TF B A A0031121 TA Ambient temperature TF Medium temperature A Maximum permissible m...

Page 45: ...2 1 DIN 2501 PN100 PN63 PN40 PN16 0 10 20 30 40 50 60 70 80 90 100 0 200 400 600 800 1200 1300 1400 bar psi 0 80 160 240 320 400 C F 200 150 100 50 0 50 200 100 320 80 A0029636 EN 19 With flange mater...

Page 46: ...th the device order code for Additional Approval option LN Type test containment DN Secondary containment pressure rating designed with a safety factor 4 Secondary containment burst pressure mm in bar...

Page 47: ...82 System pressure It is important that cavitation does not occur or that gases entrained in the liquids do not outgas This is prevented by means of a sufficiently high system pressure For this reason...

Page 48: ...bility of the measuring system is not affected by plant vibrations Custody transfer measurement The measuring device is optionally tested in accordance with OIML R81 R117 and has an EC evaluation cert...

Page 49: ...up to 30 mm 3 dependent on respective process connection Order code for Housing option A Aluminum coated Ex d DN A 1 B 1 C D 2 E 2 F G H I K L mm mm mm mm mm mm mm mm mm mm mm mm 25 200 141 59 169 68...

Page 50: ...382 790 408 2 80 200 141 59 169 68 101 43 5 409 933 524 2 100 200 141 59 169 68 101 68 9 435 1090 655 2 1 Depending on the cable gland used values up to 30 mm 2 Dependent on the respective process co...

Page 51: ...82 5 840 100 235 190 8 22 24 107 1 1128 Surface roughness flange EN 1092 1 Form B1 DIN 2526 Form C Ra 3 2 to 12 5 m Flange according to EN 1092 1 DIN 2501 PN 40 with reduction in nominal diameter 1 44...

Page 52: ...25 110 79 4 4 15 7 14 2 26 7 440 50 150 120 7 4 19 1 19 1 52 6 715 80 190 152 4 4 19 1 23 9 78 0 840 100 230 190 5 8 19 1 23 9 102 4 1128 Surface roughness flange Ra 3 2 to 6 3 m Flange according to A...

Page 53: ...m B mm C mm D mm E mm L mm 25 125 88 9 4 19 1 23 9 24 3 490 50 165 127 8 19 1 31 8 49 2 742 80 210 168 3 8 22 2 40 0 73 7 900 100 275 215 9 8 25 4 48 4 97 3 1158 Surface roughness flange Ra 3 2 to 6 3...

Page 54: ...165 130 8 19 26 50 760 80 210 170 8 23 32 75 890 100 250 205 8 25 36 100 1168 Surface roughness flange Ra 1 6 to 3 2 m Flange JIS B2220 63K 1 4404 F316 F316L Order code for Process connection option...

Page 55: ...12 81 900 100 159 137 8 11 14 100 1128 3A version available order code for Additional approval option LP in conjunction with Ra 0 8 m Order code for Measuring tube material option SB Flange DIN11864 2...

Page 56: ...on LP in conjunction with Ra 0 8 m Order code for Measuring tube material option SB Tri Clamp 1 for pipe according to DIN 11866 series C with nominal diameter reduction 1 4404 316L Order code for Proc...

Page 57: ...l option LP in conjunction with Ra 0 8 m Order code for Measuring tube material option SB Threaded hygienic connection DIN11864 1 Form A for pipe according to DIN11866 series A 1 4404 316 316L Order c...

Page 58: ...Measuring tube material option SB Accessories Purge connections pressure monitoring of secondary containment rupture disk L 45 A SW 1 2 NPT 1 NPT 35 1 38 ca 75 approx 2 95 1 1 2 A A0030349 23 Enginee...

Page 59: ...s Hauser 59 Remote display and operating module DKX001 136 5 35 114 4 49 86 3 39 78 3 07 103 4 06 12 0 47 7 0 0 27 A0028921 24 Engineering unit mm in External WLAN antenna 68 2 7 93 3 6 161 6 3 A00289...

Page 60: ...dent on respective process connection Order code for Housing option A Aluminum coated Ex d DN A 1 B C D 2 E F G H I K L in in in in in in in in in in in in 1 7 87 5 55 2 32 6 65 2 68 3 98 0 60 14 23 2...

Page 61: ...4 23 22 78 8 54 2 2 7 87 5 55 2 32 6 65 2 68 3 98 1 10 15 04 31 10 16 06 2 3 7 87 5 55 2 32 6 65 2 68 3 98 1 71 16 10 36 73 20 63 2 4 7 87 5 55 2 32 6 65 2 68 3 98 2 71 17 13 42 91 25 79 2 1 Depending...

Page 62: ...28 15 3 8 27 6 63 8 0 88 1 12 3 07 33 07 4 10 04 7 87 8 0 88 1 25 4 03 44 41 Surface roughness flange Ra 125 to 248 in Flange according to ASME B16 5 Class 600 1 4404 F316 F316L Order code for Proces...

Page 63: ...option LP in conjunction with Ra 32 in Order code for Measuring tube material option SB Tri Clamp 1 for pipe according to DIN 11866 series C with nominal diameter reduction 1 4404 316L Order code for...

Page 64: ...04 45 12 3A version available order code for Additional approval option LP in conjunction with Ra 32 in Order code for Measuring tube material option SB Accessories Purge connections pressure monitori...

Page 65: ...4 06 12 0 47 7 0 0 27 A0028921 27 Engineering unit mm in External WLAN antenna 68 2 7 93 3 6 161 6 3 A0028923 28 Engineering unit mm in Weight All values weight refer to devices with EN DIN PN 40 flan...

Page 66: ...Aluminum coated glass Option L Cast stainless glass Cable entries cable glands 1 2 3 4 A0028352 29 Possible cable entries cable glands 1 Cable entry with M20 1 5 internal thread 2 Cable gland M20 1 5...

Page 67: ...Plug M12 1 Socket Stainless steel 1 4404 316L Contact housing Polyamide Contacts Gold plated brass Device plug Electrical connection Material Plug M12x1 Socket Stainless steel 1 4404 316L Contact hous...

Page 68: ...n via the integrated memory integrated HistoROM which contains the process and measuring device data and the event logbook No need to reconfigure Efficient diagnostics increase measurement availabilit...

Page 69: ...10 m 30 ft Cable touch control Another device version e g other housing material other cable length etc can be ordered via the separate product structure DKX001 The measuring device is ordered with O...

Page 70: ...ousing order code for Electrical connection Connecting cable 35 Dimensions 59 Remote operation Via HART protocol This communication interface is available in device versions with a HART output 1 2 3 5...

Page 71: ...Care AMS Device Manager SIMATIC PDM with COM DTM CDI Communication TCP IP 6 Commubox FXA195 USB 7 Field Xpert SFX350 or SFX370 8 VIATOR Bluetooth modem with connecting cable 9 Transmitter Via FOUNDATI...

Page 72: ...ment coupler PROFIBUS DP PA 5 PROFIBUS PA network 6 T box 7 Measuring device Via Modbus RS485 protocol This communication interface is available in device versions with a Modbus RS485 output 1 2 3 A00...

Page 73: ...ontrol WLAN 2 1 5 6 3 4 3 4 A0028839 1 Transmitter with integrated WLAN antenna 2 Transmitter with external WLAN antenna 3 LED lit constantly WLAN reception is enabled on measuring device 4 LED flashi...

Page 74: ...ield Device Manager FDM by Honeywell www honeywellprocess com FieldMate by Yokogawa www yokogawa com PACTWare www pactware com The associated device description files are available at www endress com...

Page 75: ...or plug in the transmitter neck part Data backup Automatic The most important device data sensor and transmitter are automatically saved in the DAT modules If the transmitter or measuring device is re...

Page 76: ...nts of the applicable EU Directives These are listed in the corresponding EU Declaration of Conformity along with the standards applied Endress Hauser confirms successful testing of the device by affi...

Page 77: ...A Class I Zone 2 AEx Ex nA IIC T5 T1 Gc Ex tb Zone 21 AEx Ex tb IIIC T C Db Sanitary compatibility 3 A approval EHEDG tested Functional safety The measuring device can be used for flow monitoring syst...

Page 78: ...ures carried out Radio approval Europe RED 2014 53 EU United States of America CFR Title 47 FCC Part 15 247 Canada RSS 247 Issue 1 Japan Article 2 clause 1 item 19 Additional country specific approval...

Page 79: ...with Class A requirements Electromagnetic compatibility EMC requirements NAMUR NE 21 Electromagnetic compatibility EMC of industrial process and laboratory control equipment NAMUR NE 32 Data retentio...

Page 80: ...cription Extended HistoROM Comprises extended functions concerning the event log and the activation of the measured value memory Event log Memory volume is extended from 20 message entries standard ve...

Page 81: ...ccessories Description Transmitter Promass 300 Transmitter for replacement or storage Use the order code to define the following specifications Approvals Output Input Display operation Housing Softwar...

Page 82: ...ions BA01202S Field Xpert SFX370 Field Xpert SFX370 is a mobile computer for commissioning and maintenance It enables efficient device configuration and diagnostics for HART and FOUNDATION Fieldbus de...

Page 83: ...read in the operating pressure value For details see Technical Information TI00426P TI00436P and Operating Instructions BA00200P BA00382P Cerabar S The pressure transmitter for measuring the absolute...

Page 84: ...IECEx Ex d Ex de XA01405D ATEX IECEx Ex ec XA01439D cCSAus XP XA01373D cCSAus Ex d Ex de XA01372D cCSAus Ex nA XA01507D INMETRO Ex d Ex de XA01468D INMETRO Ex ec XA01470D NEPSI Ex d Ex de XA01469D NEP...

Page 85: ...transfer SD01688D SD01689D Installation Instructions Contents Documentation code Installation Instructions for spare part sets Specified for each individual accessory Registered trademarks HART Regis...

Page 86: ......

Page 87: ......

Page 88: ...www addresses endress com...

Reviews: