Operating conditions: Installation
Installation instructions
Note the following points:
• No special measures such as supports are necessary. External forces are absorbed by the construction of the
instrument, for example the secondary containment.
• The high oscillation frequency of the measuring tubes ensures that the correct operation of the measuring
system is not influenced by pipe vibrations.
• No special precautions need to be taken for fittings which create turbulence (valves, elbows, T-pieces, etc.),
as long as no cavitation occurs.
• For mechanical reasons and in order to protect the pipe, it is advisable to support heavy sensors.
• Please refer to the verification ordinances for the installation conditions of the approval for custody transfer
in question.
!
Note!
The necessary steps for creating a measuring system and obtaining approval from the Standards Authorities
must be clarified with the authority for legal metrology controls responsible.
Mounting location
Entrained air or gas bubbles in the measuring tube can result in an increase in measuring errors.
Avoid
the following mounting locations in the pipe:
• Highest point of a pipeline. Risk of air accumulating.
• Directly upstream from a free pipe outlet in a vertical pipeline
a0003605
Mounting location
Notwithstanding the above, the installation proposal below permits installation in an open vertical pipeline.
Pipe restrictions or the use of an orifice with a smaller cross-section than the nominal diameter prevent the
sensor running empty while measurement is in progress.
a0003597
Installation in a down pipe (e.g. for batching applications)
1 = Supply tank, 2 = Sensor, 3 = Orifice plate, pipe restriction (see Table), 4 = Valve, 5 = Batching tank
1
2
3
4
5