Functions relevant to custody transfer
Commissioning Instructions for PTB gas approval Proline Promass 84
34
Hauser
7.18.3
Status output
Function name
No.
Description
Configuration
ASSIGN STATUS
4241 Use this function to assign a switching function to the
status output.
Options:
e.g. FAULT MESSAGE
ON-VALUE
4242 Use this function to enter the value for the switch-on
point.
User input:
e.g. 0 kg
SWITCH-ON DELAY
4243 Time period which must elapse after the switch-on
point has been reached and before the output switches.
User input:
e.g. 0.0 s
OFF-VALUE
4244 Use this function to enter the value for the switch-off
point.
User input:
e.g. 2 kg
SWITCH-OFF DELAY
4245 Time period which must elapse after the switch-off
point has been reached and before the output switches.
User input:
e.g. 0.0 s
MEASURING MODE
4246 Use this function to select the measuring mode.
Options:
e.g. STANDARD
TIME CONSTANT
4247 Time constant which determines how the frequency
output reacts to severely fluctuating flow variables.
User input:
e.g. 0.00 s