Commissioning
Proline Promag L 400 HART
94
Hauser
Value status input
The
On
option is selected in the
Status input simulation
parameter.
Select the input
signal level of the
status input for the
simulation.
• High
• Low
High
Simulation current
output 1
-
Switch simulation of
the current output
on and off.
• Off
• On
Off
Value current
output 1
The
On
option is selected in the
Current output simulation
parameter.
Enter the current
value for simulation.
• 0-20 mA:
0 to 22.5 mA
• 4-20 mA HART:
3.6 to 22.5 mA
Current value
currently measured
Simulation
frequency output
1-2
-
Switch simulation of
the frequency
output on and off.
• Off
• On
Off
Frequency value 1-2 The
On
option is selected in the
Simulation frequency output
1-2
parameter.
Enter the frequency
value for simulation.
0 to 12
500 Hz
Frequency currently
measured
Simulation pulse
output 1-2
-
Set and switch off
pulse output
simulation.
• Off
• Fixed value
• Down-count val.
If the
Fixed
value
option
is selected,
the
Pulse
width
parameter
defines the
pulse width of
the pulses
output
(
Off
Pulse value 1-2
The
Down-count. val.
option
is selected in the
Simulation
pulse output 1-2
parameter.
Enter the number of
pulses for
simulation.
0...65535
Pulse currently
measured
Switch output
simulation 1-2
-
Switch simulation of
the switch output on
and off.
• Off
• On
Off
Switch status 1-2
The
On
option is selected in the
Switch output simulation
1-2
parameter.
Select the status of
the status output for
the simulation.
• Open
• Closed
Open
Simulation device
alarm
-
Switch the device
alarm on and off.
• Off
• On
Off
10.7
Protecting settings from unauthorized access
The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code for the local display and Web browser (
• Write protection via write protection switch (