Device Functions Proline Promag 55 FOUNDATION Fieldbus
5 Block USER INTERFACE
Hauser
33
5.4.2
Function group MULTIPLEX
USER INTERFACE
C
⇒
CONTROL
CAA
⇓
MAIN LINE
CCA
⇓
ADDITIONAL LINE
CEA
⇓
INFORMATION LINE
CGA
⇒
CONFIGURATION
260
⇓
MULTIPLEX
262
Function description
USER INTERFACE
→
INFORMATION LINE
→
MULTIPLEX
ASSIGN
(2620)
Use this function to define the second reading to be displayed in the information line
alternately (every 10 seconds) with the value defined in the function ASSIGN (2600).
Options:
OFF
VOLUME FLOW IN %
MASS FLOW IN %
VOLUME FLOW BARGRAPH IN %
MASS FLOW BARGRAPH IN %
FLOW VELOCITY
OPERATING/SYSTEM CONDITIONS
FLOW DIRECTION READING
AI1 - OUT VALUE
AI2 - OUT VALUE
AI3 - OUT VALUE
AI4 - OUT VALUE
AI5 - OUT VALUE
PID - IN VALUE (controlled variable)
PID - CAS IN VALUE (external set point)
PID - OUT VALUE (manipulated variable)
DEVICE PD-TAG (tag name)
Factory setting:
OFF
!
Note!
Multiplex mode is suspended as soon as a fault / notice message is generated. The
message in question appears on the display. Once the fault is eliminated, the measuring
device resumes operation in Multiplex mode and the error message is no longer displayed
on the local display.
100%-VALUE
(2621)
!
Note!
This function is not available unless one of the following was selected in the ASSIGN
function (2620):
• VOLUME FLOW IN %
• MASS FLOW IN %
• VOLUME FLOW BARGRAPH IN %
• MASS FLOW BARGRAPH IN %
Use this function to define the flow value to be shown on the display as the 100% value.
User input:
5-digit floating-point number
Factory setting:
Nominal diameter and country dependent