Proline Promag 55 FOUNDATION Fieldbus
Commissioning
Hauser
63
6.3
Commissioning using FOUNDATION Fieldbus
Note the following points:
• The files required for commissioning and network configuration can be obtained as described on
• The device is identified by the FOUNDATION Fieldbus in the host or configuration system via
the device ID (DEVICE_ID). The DEVICE_ID is a combination of the manufacturer ID, device
type and device serial number. It is unique and can never be duplicated. The DEVICE_ID of
Promag 55 is composed as follows:
DEVICE_ID = 452B481042-XXXXXXXXXXX
452B48 = Hauser
1042 = Promag 55
XXXXXXXXXXX = device serial number (11-digit)
6.3.1
Commissioning
The following description allows step-by-step commissioning of the measuring device and all the
necessary configuration for the FOUNDATION Fieldbus:
1.
Switch on the measuring device.
2.
Note the DEVICE_ID on the device nameplate
3.
Open the configuration program.
4.
Load the device description file or CFF file into the host system or into the configuration
program. Ensure you use the correct system files. Refer to the example on
59.
The first time it is connected Promag 55 reports as follows:
– E+H_PROMAG_55_ xxxxxxxxxxx (tag name PD-TAG)
– 452B481042- xxxxxxxxxxx (Device_ID)
– Block structure:
Display text (xxx... = serial number)
Base index
Description
RESOURCE_xxxxxxxxxxx
400
Resource Block
TRANSDUCER_FLOW_xxxxxxxxxxx
1400
"Flow" Transducer Block
TRANSDUCER_DIAG_xxxxxxxxxxx
1600
"Diagnosis" Transducer Block
TRANSDUCER_DISP_xxxxxxxxxxx
1800
"Display" Transducer Block
TRANSDUCER_TOT_xxxxxxxxxxx
1900
"Totalizer" Transducer Block
TRANSDUCER_SCON_xxxxxxxxxxx
2400
"Solids Content Flow" Transducer Block
TRANSDUCER_ADVD_xxxxxxxxxxx
2500
"Advanced Diagnostics" Transducer Block
ANALOG_INPUT_1_xxxxxxxxxxx
500
Analog Input function block 1
ANALOG_INPUT_2_xxxxxxxxxxx
550
Analog Input function block 2
ANALOG_INPUT_3_xxxxxxxxxxx
600
Analog Input function block 3
ANALOG_INPUT_4_xxxxxxxxxxx
650
Analog Input function block 4
ANALOG_INPUT_5_xxxxxxxxxxx
700
Analog Input function block 5
ANALOG_OUTPUT_xxxxxxxxxxx
2300
Analog Output function block (AO)
DISCRETE_OUTPUT_xxxxxxxxxxx
900
Discrete Output function block (DO)
PID_xxxxxxxxxxx
1000
PID function block (PID)
ARITHMETIC_xxxxxxxxxxx
1100
Arithmetic function block (ARTH)
INPUT_SELECTOR_xxxxxxxxxxx
1150
Input Selector function block (ISEL)
SIGNAL_CHARACT_xxxxxxxxxxx
1200
Signal Characterizer function block (CHAR)
INTEGRATOR_xxxxxxxxxxx
1250
Integrator function block (INTG)