PROline Promag 23
9 Trouble-shooting
Hauser
69
9.5
Response of outputs to errors
!
Note:
The failsafe mode of totalizers, current, pulse and frequency outputs can be customized
by means of various functions in the function matrix. You will find detailed information on
these procedures in the “Description of Device Functions” manual.
Positive zero return and failsafe mode:
You can use positive zero return to reset the signals of the current, pulse and frequency
outputs to their fallback value, for example when measuring has to be interrupted
while a pipe is being cleaned. This function takes priority over all other device functions:
simulations, for example, are suppressed.
Failsafe mode of outputs and totalizers
Process/system error is current
Positive zero return is activated
"
Caution:
System or process errors defined as “Notice messages” have no effect whatsoever on the
inputs and outputs. See the information on Page 45 ff.
Current output
MAXIMUM CURRENT
HART 4–20 mA (NAMUR)
o
22 mA
HOLD VALUE
Last valid value (preceding occurrence of the
fault) is output.
ACTUAL VALUE
Fault is ignored, i.e. normal measured-value
output on the basis of ongoing flow measure-
ment.
Output signal corresponds to
“zero flow”
Pulse output
FALLBACK VALUE
Signal output
o
no pulses
HOLD VALUE
Last valid value (preceding occurrence of the
fault) is output.
ACTUAL VALUE
Fault is ignored, i.e. normal measured value
output on the basis of ongoing flow measure-
ment.
Output signal corresponds to
“zero flow”
Frequency output
FALLBACK VALUE
Signal output
o
0 Hz
FAILSAFE LEVEL
Output of the frequency specified in the
FAILSAFE VALUE function.
HOLD VALUE
Last valid value (preceding occurrence of the
fault) is output.
ACTUAL VALUE
Fault is ignored, i.e. normal measured value
output on the basis of ongoing flow measure-
ment.
Output signal corresponds to
“zero flow”
Summary of Contents for PROline promag 23
Page 4: ...Contents PROline Promag 23 4 Endress Hauser ...
Page 10: ...2 Identification PROline Promag 23 10 Endress Hauser ...
Page 30: ...3 Installation PROline Promag 23 30 Endress Hauser ...
Page 40: ...4 Wiring PROline Promag 23 40 Endress Hauser ...
Page 52: ...5 Operation PROline Promag 23 52 Endress Hauser ...
Page 56: ...6 Commissioning PROline Promag 23 56 Endress Hauser ...
Page 58: ...7 Maintenance PROline Promag 23 58 Endress Hauser ...
Page 102: ...10 Technical data PROline Promag 23 102 Endress Hauser ...