Proline 200 FOUNDATION Fieldbus
Electrical connection
Hauser
15
2
1
3
4
7
8
6
6
6
6
5
6
6
5
A0028768
1
Connection example for FOUNDATION Fieldbus
1
Control system (e.g. PLC)
2
Power conditioner (FOUNDATION Fieldbus)
3
Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements;
observe cable specifications
4
T-box
5
Measuring device
6
Local grounding
7
Bus terminator
8
Potential equalization conductor
5.1.6
Requirements for the supply unit
Supply voltage
Transmitter
An external power supply is required for each output.
Order code for "Output"
Minimum
terminal voltage
Maximum
terminal voltage
Option
E
: FOUNDATION Fieldbus, pulse/frequency/
switch output
≥ DC 9 V
DC 32 V
1)
For device version with SD03 local display: The terminal voltage must be increased by DC 0.5 V if backlighting is
used.