Operating menu
Tankside Monitor NRF81
190
Hauser
Description of parameters
Navigation
Setup → Advanced setup → Application → Tank calculation
→ HyTD
HyTD correction value
Navigation
Setup → Advanced setup → Application → Tank calculation → HyTD → HyTD
correction value
Description
Shows the correction value from the Hydrostatic Tank Deformation.
Additional information
Read access
Operator
Write access
-
HyTD mode
Navigation
Setup → Advanced setup → Application → Tank calculation → HyTD → HyTD mode
Description
Activates or deactivates the calculation of the Hydrostatic Tank Deformation.
Selection
• No
• Yes
Factory setting
No
Additional information
Read access
Operator
Write access
Maintenance
Starting level
Navigation
Setup → Advanced setup → Application → Tank calculation → HyTD → Starting level
Description
Defines the starting level for the Hydrostatic Tank Deformation. Levels below this value
are not corrected.
User entry
0 to 5
000 mm
Factory setting
500 mm
Additional information
Read access
Operator
Write access
Maintenance