Operating menu
Tankside Monitor NRF81
116
Hauser
Additional information
Read access
Operator
Write access
-
15.2.3 "Density" submenu
Navigation
Operation → Density
Observed density
Navigation
Operation → Density → Observed density
Description
Calculated density of the product.
Additional information
Read access
Operator
Write access
-
This value is calculated from different measured variables depending on the selected
calculation method → 188.
Vapor density
Navigation
Operation → Density → Vapor density
Description
Defines the density of the gas phase in the tank.
User entry
0.0 to 500.0 kg/m³
Factory setting
1.2 kg/m³
Additional information
Read access
Operator
Write access
Maintenance
Air density
Navigation
Operation → Density → Air density
Description
Defines the density of the air surrounding the tank.
User entry
0.0 to 500.0 kg/m³