Operating menu
Micropilot NMR84
164
Hauser
"HART output" submenu
Navigation
Setup → Advanced setup → Communication → HART output
"Configuration" submenu
Navigation
Setup → Advanced setup → Communication → HART output
→ Configuration
System polling address
Navigation
Setup → Advanced setup → Communication → HART output → Configuration
→ Polling address
Description
Device address for HART communication.
User entry
0 to 63
Factory setting
15
Additional information
Read access
Operator
Write access
Maintenance
No. of preambles
Navigation
Setup → Advanced setup → Communication → HART output → Configuration → No.
of preambles
Description
Defines the number of preambles in the HART telegram.
User entry
5 to 20
Factory setting
5
Additional information
Read access
Operator
Write access
Maintenance
PV source
Navigation
Setup → Advanced setup → Communication → HART output → Configuration → PV
source
Description
Decides, if the PV configuration is according to an analog output (HART slave) or
customized (in case of HART tunneling only).