Operating menu
Micropilot NMR84
120
Hauser
Additional information
Read access
Operator
Write access
Maintenance
Tank level
Navigation
Setup → Tank level
Description
Shows the distance from the zero position (tank bottom or datum plate) to the product
surface.
Additional information
Read access
Operator
Write access
-
Set level
Navigation
Setup → Set level
Description
If the level measured by the device does not match the actual level obtained by a manual
dip, enter the correct level into this parameter.
User entry
0 to 10
000.00 mm
Factory setting
0 mm
Additional information
Read access
Operator
Write access
Maintenance
The device adjusts the
Empty
parameter (→ 119) according to the entered value, such
that the measured level will match the actual level.
• After the change of the
Empty
Table mode
parameter
(→ 208) is automatically set to
Disable
.
• If
Empty
has been changed by more than 20 mm (0.8 in), it is recommended to
delete the dip table.
• The dip table values are not affected by a change of the
Empty
parameter.
Confirm distance
Navigation
Setup → Confirm distance
Description
Specify, whether the measured distance matches the real distance. Depending on the
selection the device automatically sets the range of mapping.