Mounting
Micropilot M FMR 231 with HART/4...20 mA
20
E Hauser
3.4.3
Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display
and the terminal compartment. Proceed as follows to turn the housing to the required
position:
•
Undo the fixing screws (1)
•
Turn the housing (2) in the required direction
•
Tighten up the fixing screws (1)
L00-FMR2xxxx-17-00-00-en-010
3.5
Post-installation check
After the measuring instrument has been installed, perform the following checks:
•
Is the measuring instrument damaged (visual check)?
•
Does the measuring instrument correspond to the measuring point specifications
such as process temperature/pressure, ambient temperature, measuring range, etc.?
•
Is the flange marking correctly aligned? (
→
Page 10)
•
Have the flange screws been tightened up with the respective tightening torque?
•
Are the measuring point number and labeling correct (visual check)?
•
Is the measuring instrument adequately protected against rain and direct sunlight
(
→
Page 59)?
1
1
2
2
F12 / F23 housing
T12 housing
allen key
4 mm/0.1”