Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
158
Hauser
Switch-on value
Navigation
Setup → Advanced setup → Switch output → Switch-on value
Prerequisite
Switch output function (→ 156)
=
Limit
Description
Enter measured value for the switch-on point.
User entry
Signed floating-point number
Factory setting
0
Additional information
The switching behavior depends on the relative position of the
Switch-on value
and
Switch-off value
parameters:
Switch-on value > Switch-off value
– The output is closed if the measured value is larger than
Switch-on value
.
– The output is opened if the measured value is smaller than
Switch-off value
.
t
t
A
B
C
D
A0015585
A
Switch-on value
B
Switch-off value
C
Output closed (conductive)
D
Output opened (non-conductive)
Switch-on value < Switch-off value
– The output is closed if the measured value is smaller than
Switch-on value
.
– The output is opened if the measured value is larger than
Switch-off value
.
Summary of Contents for Micropilot FMR56
Page 197: ......
Page 198: ...www addresses endress com 71344036 71344036 ...