Commissioning (block-based operation)
Micropilot FMR51, FMR52 FOUNDATION Fieldbus
84
Hauser
12.5 Configuration of a level measurement
The
Setup
method can also be used to configure the measurement. It is called up via
the SETUP (TRDSUP) Transducer Block.
F
L
D
E
100%
0%
R
A0016933
R = Reference point of the measurement E = Empty calibration (= Zero point)
D = Distance
F = Full calibration (= span)
L = Level
Step
Block
Parameter
Action
1
SETUP (TRDSUP)
Distance unit
(distance_unit)
Select distance unit.
Selection:
• 1010: m
• 1013: mm
• 1018: ft
• 1019: in
2
SETUP (TRDSUP)
Tank type (tank_type)
Select tank type.
Selection:
• 1271: Process vessel with agitator
• 1272: Process vessel standard
• 1273: Storage vessel
• 1274: Wave guide antenna
• 1279: Sphere
• 32816: Bypass / pipe
• 33013: Open channel
• 33094: Stilling well
3
SETUP (TRDSUP)
Tube diameter
(tube_diameter)
Enter the diameter of the bypass or stilling well.
4
SETUP (TRDSUP)
Medium group
(medium_group)
Select medium group.
Selection:
• 316: water based (DC>4)
• 256: other (DC≥ 1.9)
5
SETUP (TRDSUP)
Empty calibration
(empty_calibration)
Enter the distance E between the reference point
R and the minimum level (0%).
6
SETUP (TRDSUP)
Full calibration
(full_calibration)
Enter distance F between the minimum (0%) and
maximum (100%) level.
7
SETUP (TRDSUP)
Level (level)
Displays the measured level L.