Micropilot FMR51, FMR52 HART
System integration via HART protocol
Hauser
65
9
System integration via HART protocol
9.1
Overview of the Device Description files (DD)
Manufacturer ID
0x11
Device type
0x1128
HART specification
7.0
DD files
For information and files see:
•
www.endress.com
•
www.hartcomm.org
9.2
Measured values via HART protocol
On delivery the following measruing values are assigned to the HART device varaibles:
Device variable
Measuring value
Primary variable (PV)
Level linearized
Secondary variable (SV)
Unfiltered distance
Tertiary variable (TV)
Absolute echo amplitude
Quaternary variable (QV)
Relative echo amplitude
The allocation of the device variables can be changed in the operating menu:
Expert → Communication → Output
In a HART multidrop loog only one device may use the output current for signal
transmission. For all other devices the follwing must be set:
•
Fixed current
•
=
4 mA
Summary of Contents for Micropilot FMR50