Installation
Micropilot FMR51, FMR52 HART
32
Hauser
6.6.2
Example for the construction of a bypass
100%
0%
A
A
A
A-A
mm (in)
200
(7.87)
200
(7.87)
200
(7.87)
200
(7.87)
B
5
4
4
1
2
C
3
3
≤
1 (0.04)
A0019010
A
Micropilot FMR50/FMR51/FMR52/FMR54: Horn 80mm(3")
B
Full bore ball valve
C
Minimum distance to upper connection pipe: 400 mm (15,7 in)
1
Marking for axial alignment
2
e.g. welding neck flange DIN2633
3
Diameter of the connection pipes as small as possible
4
Do not weld through the pipe wall; the inside of the bypass must remain smooth.
5
Diameter of opening of ball valve must always be equivalent to pipe diameter. Avoid edges and constrictions.