Micropilot FMR20 HART
Operating menu
Hauser
81
Changing velocity
Navigation
Setup → Advanced setup → Changing vel.
Description
Selection of the expected draining or filling speed of the measured level.
Selection
• Slow <10 cm (0,4 in)/min
• Standard <1 m (40 in)/min
• Fast >1 m (40 in)/min
• No filter / test
First Echo sensitivity
Navigation
Setup → Advanced setup → First Echo sens.
Description
This parameter describes the band for First Echo evaluation.
Is measured / calculated down from the peak of the current level echo.
Options to select from:
- Low
The band for the first echo evaluation is very narrow. The evaluation stays longer at the
found echo respectively does not jump to the next Echo or distortion signal.
- Medium
The band for the first echo evaluation has an average width.
- High
The band for the first echo evaluation is broad. The evaluation jumps earlier to the next
echo or distortion signal.
Selection
• Low
• Medium
• High
Output mode
Navigation
Setup → Advanced setup → Output mode
Description
Select output mode between:
Ullage =
The remaining space in the tank or silo is indicated.
or
Level linearized =
The level is indicated (more precisely: the linearized value if a linearization has been
activated).
Selection
• Ullage
• Level linearized