Installation
Micropilot FMR20 HART
20
Hauser
ensures a defined detection of the maximum level directly at the end of the tube. Due to
the fact that the Blocking distance is inside the tube, multiple echoes are not analyzed.
Configuration parameters for flooding protection tube
Configuring the blocking distance when using the flooding protection tube
‣
Navigate to: Main menu → Setup → Advanced setup → Blocking distance
Enter 100 mm (4 in).
Perform a mapping after the flooding protection tube has been installed and the
blocking distance has been configured
1. Navigate to: Setup → Confirm distance
Compare the distance displayed with the actual value in order to start the
recording of an interference echo map.
2. Navigate to: Setup → Mapping end point
This parameter determines the distance up to which the new mapping is to be
recorded.
3. Navigate to: Setup → Present mapping
Displays the distance up to which a mapping has already been recorded.
5.1.9
Installation with mounting bracket, adjustable
The mounting bracket can be ordered as an accessory or together with the device via the
product structure "Accessory enclosed".
A0046287
12
Installation with mounting bracket, adjustable
• Wall or ceiling installation is possible.
• Using the mounting bracket, position the antenna so that it is perpendicular to the
product surface.
NOTICE
There is no conductive connection between the mounting bracket and transmitter
housing.
Electrostatic charging possible.
‣
Integrate the mounting bracket in the local potential equalization system.
5.1.10 Cantilever installation, with pivot
The cantilever, wall bracket and mounting frame are available as accessories.