Micropilot FMR20 HART
Installation
Hauser
15
L
D
L
D
A0046282
4
Nozzle installation
The maximum nozzle length
L
depends on the nozzle diameter
D
.
Please note the limits for the diameter and length of the nozzle.
80 mm (3 in) antenna, installation inside nozzle
• D: min. 120 mm (4.72 in)
• L: max. 205 mm (8.07 in) + D × 4.5
80 mm (3 in) antenna, installation outside nozzle
• D: min. 80 mm (3 in)
• L: max. D × 4.5
5.1.3
Position for installation on a vessel
BD
A
1
2
3
A0045323
5
Installation position on a vessel
• If possible install the sensor so that its lower edge is inside the vessel.
• Recommended distance
A
wall - nozzle outer edge: ~ ¹⁄₆ of the vessel diameter. Under no
circumstances should the device be mounted closer than 15 cm (5.91 in) to the vessel
wall.
• Do not install the sensor in the middle of the vessel.