15.7 Relay outputs
Electrical specification
Relay types
• 2 x changeover contact, coupled with binary output (optional)
• 1 single-pin changeover contact (alarm relay)
Maximum load
• Alarm relay: 0.5 A
• All other relays: 2.0 A
Relay switching capacity
Power unit (Alarm relay)
Switching voltage
Load (max.)
Switching cycles (min.)
230 V AC, cosΦ = 0.8 to 1
0.1 A
700,000
0.5 A
450,000
24 V DC, L/R = 0 to 1 ms
0.1 A
500,000
0.5 A
350,000
Relay coupled with binary output
Switching voltage
Load (max.)
Switching cycles (min.)
230 V AC, cosΦ = 0.8 to 1
5 A
100,000
24 V DC, L/R = 0 to 1 ms
5 A
100,000
15.8 Protocol-specific data
HART
Manufacturer ID
11
h
Device type
119D
h
Device revision
001
h
Device description files (DD/DTM)
www.endress.com/hart
Device Integration Manager DIM
Device variables
Supported features
PDM DD, AMS DD, DTM,
Modbus RS485
Protocol
RTU/ASCII
Function codes
03, 04, 06, 08, 16, 23
Broadcast support for function codes
06, 16, 23
Output data
16 measured values (value, unit, status), 8 digital values (value,
status)
Input data
4 setpoints (value, unit, status), 8 digital values (value, status),
diagnostic information
Supported features
Address can be configured using switch or software