These Brief Operating Instructions are not a substitute for the Operating Instructions pertaining to the device.
Detailed information is provided in the Operating Instructions and other documentation.
Available for all device versions via:

• Internet: www.endress.com/deviceviewer

• Smartphone/tablet: Hauser Operations app

Basic safety instructions

Requirements for the personnel

The personnel performing installation, commissioning, diagnostics and

maintenance must satisfy the following requirements:
• Trained, qualified specialists: must have a relevant qualification for this

specific function and task

• Are authorized by the plant owner/operator

• Are familiar with federal/national regulations

• Before starting work: read and understand the instructions in the manual and

supplementary documentation as well as the certificates (depending on the

application)

• Follow instructions and comply with basic conditions

Intended use

The device described in this manual may be used only as a point level switch for

liquids. The device is suitable for use in areas with strict hygiene requirements.

Incorrect use of the device may pose a hazard.

To ensure that the device remains in proper condition for the operation time:

• Use the device only for media to which the wetted materials have an adequate

level of resistance

• Comply with the limit values, see the "Technical data" section of the Operating

Instructions

Operational safety

Danger of injury!

Operate the device only if it is in proper technical condition, free from errors

and faults.

The operator is responsible for the interference-free operation of the device.

Mounting

The mounting process is illustrated in the following section on the basis of

sample configurations. For detailed information, see the Operating

Instructions.

Mounting requirements

L1

L2

L3

L4

A

B

2

1

32 mm

32 mm

3

3

A

Device with weld-in adapter

B

Device in customer socket

1

Flat seal

2

Weld-in adapter

3

Tuning fork

L1 With G 1" thread: 66,4 mm (2,61 in) / With G ¾" thread: 63,9 mm (2,52 in)

L2 With G 1" thread: 48,0 mm (1,89 in) / With G ¾" thread: 38,0 mm (1,5 in)

L3 With G 1" thread: 66,4 mm (2,61 in)

L4 With G 1“ thread:47,9 mm (1,8 in)

Installation is possible in any position in a vessel, pipe or tank under the

following conditions:

• When installed horizontally in a vessel, the tuning fork may be located in an

installation socket only if liquids with low viscosity (< 2

 

000 mPa⋅s) are used.

• Minimum diameter of installation socket: 50 mm (2.0 in)

• Select a maximum length for the installation socket that enables the tuning

fork to project freely into the vessel.

• Ensure that there is sufficient distance between the expected buildup on the

tank wall and the fork. Recommended distance from wall ≥10 mm (0.39 in).

Important process conditions

Pressure and temperature (maximum):

• With weld-in adapter

• +25 bar (+362 psi) at +150 °C (+302 °F)

• +40 bar (+580 psi) at +100 °C (+212 °F)

• In customer socket

+40 bar (+580 psi) at +150 °C (+302 °F)

Operating altitude:

Up to 2 000 m (6 600 ft) above sea level

In the case of seals used at the customer site, pay attention to the

temperature and pressure specifications.

Products

Solutions

Services

Brief Operating Instructions

Liquiphant FTL33

Point level switch for liquids in the food industry