Wiring
Levelflex M FMP40 with HART/4...20 mA
30
Hauser
4.2
Connecting the measuring unit
Connection compartment
Three housings are available:
• Aluminum housing F12 with additionally sealed connection compartment for:
– Standard
– Ex ia
– Dust ignition-proof
• Aluminum housing T12 with separate connection compartment for:
– Standard
– Ex e
– Ex d
– Ex ia (with overvoltage protection)
– Dust ignition-proof
• Stainless steel 316L housing F23 for:
– Standard
– Ex ia
– Dust ignition-proof
L00-FMR2xxxx-04-00-00-en-019
The device data are given on the nameplate together with important information regarding the
analog output and power supply. Housing rotation with regard to the wiring, see "Turning the
housing" on
HART load
Minimum load for HART communication: 250
Ω
Ground connection
A good ground connection has to be made to the ground terminal on the outside of the housing in
order to achieve EMC immunity.
Cable gland
Terminals
For wire cross-sections of 0.5 to 2.5 mm
2
1
1
2
2
3
3
4
4
1 2
3 4
sealed terminal
compartment
F12 housing
F23 housing
T12 housing
Type
Clamping area
Standard, Ex ia, IS
Plastic M20x1.5
5 to 10 mm
Ex em, Ex nA
Metal M20x1.5
7 to 10.5 mm
Summary of Contents for Levelflex M FMP40
Page 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Page 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Page 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Page 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Page 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...