Proline Promag P 500 HART
Electrical connection
Hauser
61
Current input
3
1
4
2
A0028915
32
Connection example for 4 to 20 mA current input
1
Power supply
2
External measuring device (for reading in pressure or temperature, for instance)
3
Transmitter: Observe input values
Status input
1
2
3
A0028764
33
Connection example for status input
1
Automation system with status output (e.g. PLC)
2
Power supply
3
Transmitter: Observe input values
7.6
Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection,
Type 4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following
steps after the electrical connection:
1. Check that the housing seals are clean and fitted correctly.
2. Dry, clean or replace the seals if necessary.
3. Tighten all housing screws and screw covers.
4. Firmly tighten the cable glands.