Operation
Gammapilot M FMG60 FOUNDATION Fieldbus
54
Hauser
3. Configure the Transducer block, Diagnostic block and Display block
•If necessary, change the block tag (right-click the tree)
•Set MODE_BLK_TARGET to Out-of-Service
•If necessary, assign a new tag description (TAG_DESC)
•Configure the device as described in the "Basic setup" section
•Set MODE_BLK_TARGET to AUTO
4. Configure the Analog Input block
•If necessary, change the block tag (right-click the tree)
•Set MODE_BLK_TARGET to Out-of-Service
•If necessary, assign a new tag description (TAG_DESC)
•Set channel to measured value or distance
•Set L_TYPE to "DIRECT" if the OUT value is to be indicated in technical units, e.g.
ft; set L_TYPE to "INDIRECT" if the OUT value is to be scaled
•Set the desired output damping in PV_TIME
•If necessary, set the advisory and critical alarms
•Set MODE_BLK_TARGET to AUTO
5. Link the function blocks in the function block editor
6. Download the configuration (Configure menu)
7. If necessary, check the configuration using the SIMULATE function
6.6.11 Start index list
Block
Start index
Resource block
400
Analog Input 1 function block
500
Analog Input 2 function block
600
PID function block
700
Arithmetic function block
800
Input Selector function block
900
Signal Characterizer function block
1000
Integrator function block
1100
Transducer block
2000
Diagnostic block
2200
Display block
2400