Installation
Gammapilot M FMG60 FOUNDATION Fieldbus
18
Hauser
Examples
A
B
C
D
E
F
1
A0018074
A
Vertical cylinder; the Gammapilot M is mounted vertically with the detector head pointing downwards, the
gamma ray is aligned to the measuring range.
B
Cascading of multiple Gammapilot M devices; there is no gap between the measuring ranges
C
Incorrect: Gammapilot M mounted inside the tank insulation
D
Conical vessel outlet (here with sun protection cover)
E
Horizontal cylinder (here with sun protection cover)
F
Correct: tank insulation removed for Gammapilot M
1
Support
4.2.3
Installation conditions for point level detection
Conditions
• For point level detection, the Gammapilot M is generally mounted horizontally at the
height of the desired level limit.
• The angle of emission of the source container must be exactly aligned to the measuring
range of the Gammapilot M. Observe the measuring range marks of the Gammapilot M.
• The source container and the Gammapilot M should be mounted as close to the vessel as
possible. Any access to the beam must be blocked to ensure that it is not possible to
reach into this area.
• The Gammapilot M should be protected against direct sunlight in order to increase its
service life. Use a protective cover if necessary.
• The mounting device FHG60 or an equivalent mounting device should be used to secure
the Gammapilot M → 86
The mounting device must be installed in such a way as to withstand the weight of the
Gammapilot M under all anticipated operating conditions (e.g. vibrations). → 17
More information with regard to the safety-related use of the Gammapilot M can be
found in the Functional Safety Manual SD00230F/00/EN and SD00324F/00/EN.