Source container FQG60
16
Hauser
Mounting position for level
measurement
A0018494
To guarantee the operation of the
switch-ON/switch-OFF function,
upside down installation or similar is
only permitted if it can be ensured
that no particles or high-viscosity
liquids can enter the area of the
shutter (see graphic).
E
IN
O
N
E
IN
O
N
A0018502
1
FQG60; Feature 240 "Emission Angle; Application",
Option model 5 "40 deg; level"
2
FMG60
The source container must be
mounted at the height of, or slightly
above, the maximum level for
continuous level measurement.
The radiation must be aligned exactly
with the compact transmitter
mounted opposite. The source
container and compact transmitter
should be mounted as close as
possible to the product vessel to avoid
control zones.
A0018503
1
FQG60; Feature 240 "Emission Angle; Application",
Option model 5 "40 deg; level"
2
FMG60
A distance between the source
container and the product vessel
often cannot be avoided if the
measuring range is large and the
container diameter small. This space
must then be blocked off and marked.
E
IN
O
N
E
IN
O
N
40°
1
2
2
E
IN
O
N
E
IN
O
N
40°
1