Brief Operating Instructions

Micropilot FMR50

FOUNDATION Fieldbus

Free space radar

These Instructions are Brief Operating Instructions; they are

not a substitute for the Operating Instructions pertaining to

the device.
Detailed information about the device can be found in the

Operating Instructions and the other documentation:

Available for all device versions via:

• Internet: 

www.endress.com/deviceviewer

• Smart phone/tablet: 

Hauser Operations App

KA01124F/00/EN/03.22-00

71575724

2022-08-01

Summary of Contents for FOUNDATION Fieldbus Micropilot FMR50

Page 1: ...s they are not a substitute for the Operating Instructions pertaining to the device Detailed information about the device can be found in the Operating Instructions and the other documentation Availab...

Page 2: ...d cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 2 About this document 2 1 Symbols used 2 1 1 Safety symbols DA...

Page 3: ...ls that must be connected to ground prior to establishing any other connections The ground terminals are located on the inside and outside of the device Interior ground terminal protective earth is co...

Page 4: ...ng device described in these Operating Instructions is intended for continuous non contact level measurement in liquids pastes and sludges Due to its operating frequency of approx 26 GHz a maximum rad...

Page 5: ...n the sensor may reach a temperature close to the medium temperature Danger of burns from contact with surfaces In the event of elevated fluid temperatures ensure protection against contact to prevent...

Page 6: ...m meets the legal requirements of the applicable EAC guidelines These are listed in the corresponding EAC Declaration of Conformity along with the standards applied The manufacturer confirms successfu...

Page 7: ...port the measuring device to the measuring point in its original packaging or by the process connection Always secure lifting equipment slings eyes etc to the process connection and never to the elect...

Page 8: ...wall to nozzle outer edge 1 6 of the vessel diameter However the device must not under any circumstances be mounted closer than 15 cm 5 91 in to the tank wall 1 Use of a weather protection cover prote...

Page 9: ...rientation 5 3 Internal vessel fittings A0018944 Avoid the location of internal fittings limit switches temperature sensors struts vacuum rings heating coils baffles etc inside the signal beam Take in...

Page 10: ...defined as the angle at which the energy density of the radar waves reaches half the value of the maximum energy density 3dB width Microwaves are also emitted outside the signal beam and can be refle...

Page 11: ...6 9 ft 20 m 66 ft 8 14 m 27 ft 3 50 m 11 ft 2 80 m 9 2 ft 25 m 82 ft 10 17 m 33 ft 4 37 m 14 ft 3 50 m 11 ft 30 m 98 ft 5 25 m 17 ft 4 20 m 14 ft 35 m 115 ft 6 12 m 20 ft 4 89 m 16 ft 40 m 131 ft 7 00...

Page 12: ...perties higher nozzles are also possible The maximum nozzle length Hmax depends on the nozzle diameter D D H max A0023612 D Hmax 40 mm 1 5 in 200 mm 7 9 in 50 mm 2 in 250 mm 9 9 in 80 mm 3 in 300 mm 1...

Page 13: ...ation system 2 to prevent the electronics from heating as a result of thermal radiation or convection The insulation should not be higher than the neck of the device 1 5 8 Turning the transmitter hous...

Page 14: ...nterclockwise 2 Unscrew the electronics compartment cover and check the cover seal replace it if necessary 5 9 2 Turning the display module 1 2 A0036401 1 Pull out the display module with a gentle rot...

Page 15: ...1 2 2 5 Nm 3 mm A0021451 1 Screw down the cover of the electronics compartment 2 Turn the securing clamp 90 in the clockwise direction and using an Allen key 3 mm tighten the screw of the securing cl...

Page 16: ...nd 4 without integrated overvoltage protection 3 Connection switch output open collector terminals 3 and 4 with integrated overvoltage protection 4 Connection PROFIBUS PA FOUNDATION Fieldbus terminals...

Page 17: ...tput 1 Approval 2 Terminal voltage E 2 wire FOUNDATION Fieldbus switch output G 2 wire PROFIBUS PA switch output Non Ex Ex nA Ex nA ia Ex ic Ex ic ia Ex d ia XP Ex ta DIP CSA GP 9 to 32 V 3 Ex ia IS E...

Page 18: ...Connect the potential matching line to the outer ground terminal before applying the power supply Required tools accessories For devices with a cover lock Allen key AF3 Wire stripper When using strand...

Page 19: ...sing shielded cables Connect the cable shield to the ground terminal 6 2 3 Plug in spring force terminals The electrical connection of device versions without an integrated overvoltage protection is v...

Page 20: ...onfiguration program The Cff file Common File Format cff The device description DD is in one of the following formats Device description format 4 sym ffo Device description format 5 sy5 ff5 Data for d...

Page 21: ...device for the measuring task and for the FF system 7 3 Device identification and addressing FOUNDATION Fieldbus identifies the device using its identification code device ID and automatically assigns...

Page 22: ..._TRANSFER_ TRDHROM xxxxxxxxxxx ANALOG_INPUT_1_ AI xxxxxxxxxxx ANALOG_INPUT_2_ UNK xxxxxxxxxxx DISCRETE_INPUT_ DI xxxxxxxxxxx MULTIPLE_AO_ MAO xxxxxxxxxxx ARITHMETIC_ AR xxxxxxxxxxx INPUT_SELECTOR_ ISE...

Page 23: ...iscrete output block MDO 1 PID block PID 1 arithmetic block AR 1 signal characterizer block SC 1 input selector block ISEL 1 integrator block IT 1 analog alarm block AAL In addition to the pre instant...

Page 24: ...NFIG SETUP SERVICE_SENSOR PV SV ESC OPEN OPEN E Device_01 F mm 4841 000 A0017217 9 Block configuration when device is delivered S Sensor PV Primary value level linearized SV Secondary value distance 7...

Page 25: ...rce block and allows the parameters of the electronic nameplate Electronic Name Plate to be changed Setup This method is located in the SETUP transducer block and is used for basic configuration of th...

Page 26: ...and error symbol if an error is active 1 2 Measured value symbols 1 3 Measured value 1 4 Unit 2 Measured value display bar graph 1 value 2 1 Bar graph for measured value 1 2 2 Measured value 1 includi...

Page 27: ...2 Display module 1 Operating keys Key assignment Key Navigate down in the picklist Edit the numerical values or characters within a function Key Navigate up in the picklist Edit the numerical values o...

Page 28: ...er setting key and key press and hold keys simultaneously Increases the contrast darker setting 9 2 Opening the context menu Using the context menu the user can call up the following menus quickly and...

Page 29: ...ial measuring conditions For converting the measured value scaling linearization For scaling the output signal Diagnostics Contains the most important parameters for diagnosing the condition of the de...

Page 30: ...0 Operation Setup Main menu 0104 1 Display language English Espa ol Fran ais Display language English Deutsch 0104 1 Espa ol Fran ais Display language English Deutsch 0104 1 Betrieb Setup Hauptmen Spr...

Page 31: ...respective bin type Note Workbench test deactivates all filters This option should exclusively be used for tests 4 Setup Medium group Specify media group aqueous DK 4 or other DK 1 9 5 Setup Empty ca...

Page 32: ...nce Compare the distance displayed with the actual value to start recording an interference echo map 11 Setup Advanced setup Level Level unit Select the level unit m mm ft in factory setting The react...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...www addresses endress com 71575724 71575724...