Brief Operating Instructions

Levelflex FMP50

FOUNDATION Fieldbus

Guided wave radar

These Instructions are Brief Operating Instructions; they are

not a substitute for the Operating Instructions pertaining to

the device.
Detailed information about the device can be found in the

Operating Instructions and the other documentation:

Available for all device versions via:

• Internet: 

www.endress.com/deviceviewer

• Smart phone/tablet: 

Hauser Operations App

KA01106F/00/EN/06.22-00

71565955

2022-04-05

Summary of Contents for FOUNDATION Fieldbus Levelflex FMP50

Page 1: ...s they are not a substitute for the Operating Instructions pertaining to the device Detailed information about the device can be found in the Operating Instructions and the other documentation Availab...

Page 2: ...ord cd Ser no www endress com deviceviewer Endress Hauser Operations App XXXXXXXXXXXX XXXXX XXXXXX XXX XXXX XX Serial number 1 3 2 A0023555 2 About this document 2 1 Symbols 2 1 1 Safety symbols DANGE...

Page 3: ...ls that must be connected to ground prior to establishing any other connections The ground terminals are located on the inside and outside of the device Inner ground terminal protective earth is conne...

Page 4: ...uthorized by the plant owner operator Are familiar with federal national regulations Must have read and understood the instructions in the manual and supplementary documentation Follow instructions an...

Page 5: ...module may rise up to 80 C 176 F When in operation the sensor may reach a temperature close to the medium temperature Danger of burns from contact with surfaces In the event of high medium temperatur...

Page 6: ...dicated on the nameplate is no longer valid This may also impair the safe operation of the device 3 5 1 CE mark The measuring system meets the legal requirements of the applicable EU directives These...

Page 7: ...f the information on the measuring device and on the scope of the technical documentation pertaining to the device is displayed 4 3 Storage and transport 4 3 1 Storage temperature Permitted storage te...

Page 8: ...Mounting Levelflex FMP50 FOUNDATION Fieldbus 8 Endress Hauser 5 Mounting 5 1 Mounting requirements 5 1 1 Suitable mounting position A C 1 2 3 4 B A0012606 1 Installation conditions for Levelflex...

Page 9: ...educed Distance B between rod probes and internal fittings 3 300 mm 12 in When using more than one Levelflex Minimum distance between the sensor axes 100 mm 3 94 in Distance C from the end of the prob...

Page 10: ...reliably grounded or reliably insulated Use an insulated fastening kit if it is not otherwise possible to secure the probe with a reliably insulated connection Securing rod probes In the case of WHG...

Page 11: ...1 Mounting devices with a threaded connection A0012528 Screw the device with the threaded connection into a sleeve or flange and then secure it to the process vessel via the sleeve flange When screwin...

Page 12: ...e vessel Uncoil the rope slowly and lower it carefully into the vessel Make sure the rope does not bend or buckle Avoid uncontrolled swinging of the weight as this could damage internal fittings in th...

Page 13: ...er using an Allen key 3 mm and turn the clamp 90 counterclockwise 2 Unscrew the electronics compartment cover and check the cover seal replace it if necessary Turning the display module 1 2 A0036401 1...

Page 14: ...2 2 5 Nm 3 mm A0021451 1 Screw down the cover of the electronics compartment 2 Turn the securing clamp 90 in the clockwise direction and using an Allen key 3 mm tighten the screw of the securing clamp...

Page 15: ...nd 4 without integrated overvoltage protection 3 Connection switch output open collector terminals 3 and 4 with integrated overvoltage protection 4 Connection PROFIBUS PA FOUNDATION Fieldbus terminals...

Page 16: ...ge E 2 wire FOUNDATION Fieldbus switch output G 2 wire PROFIBUS PA switch output Non hazardous Ex nA Ex nA ia Ex ic Ex ic ia Ex d ia XP Ex ta DIP CSA GP 9 to 32 V 3 Ex ia IS Ex ia Ex d ia IS XP 9 to 3...

Page 17: ...Connect the potential matching line to the outer ground terminal before applying the power supply Required tools accessories For devices with a cover lock Allen key AF3 Wire stripper When using strand...

Page 18: ...sing shielded cables Connect the cable shield to the ground terminal 6 2 3 Plug in spring force terminals The electrical connection of device versions without an integrated overvoltage protection is v...

Page 19: ...compartment 2 Turn the securing clamp 90 in the clockwise direction and using an Allen key 3 mm tighten the screw of the securing clamp on the connection compartment cover with 2 5 Nm 7 Operation opt...

Page 20: ...or symbol if an error is active 1 2 Measured value symbols 1 3 Measured value 1 4 Unit 2 Measured value display bar graph 1 value 2 1 Bar graph for measured value 1 2 2 Measured value 1 including unit...

Page 21: ...8 Display module 1 Operating keys Key assignment Key Navigate down in the picklist Edit the numerical values or characters within a function Key Navigate up in the picklist Edit the numerical values...

Page 22: ...rement should generally be completely configured Setup Mapping Mapping of interference echos Setup Advanced setup Contains additional submenus and parameters For more customized configuration of the m...

Page 23: ...l display appears Calling up the menu via the context menu 1 Open the context menu 2 Press to navigate to the desired menu 3 Press to confirm the selection The selected menu opens 8 Commissioning 8 1...

Page 24: ...0 Operation Setup Main menu 0104 1 Display language English Espa ol Fran ais Display language English Deutsch 0104 1 Espa ol Fran ais Display language English Deutsch 0104 1 Betrieb Setup Hauptmen Spr...

Page 25: ...t D Distance E Empty calibration zero point L Level F Full calibration span 1 Setup Device tag Enter device tag 2 Setup Distance unit Select the length unit 3 Setup Tank type Select tank type 4 Setup...

Page 26: ...easured level L for verification purposes 9 Setup Distance Displays the distance D between the reference point R and the level L for verification purposes 10 Setup Signal quality Displays the signal q...

Page 27: ......

Page 28: ...www addresses endress com 71565955 71565955...

Reviews: