Diagnostics and troubleshooting
Ecograph T, RSG35
56
Hauser
11.10.2 Test WebDAV Client
A test file can be sent to the selected WebDAV server in the main menu under
"Diagnostics -> Simulation -> WebDAV Client"
.
The settings for the WebDAV server to be addressed must be set beforehand under
"Setup -> Advanced setup -> Application -> WebDAV Client"
.
11.10.3 Test time synchronization/SNTP
Time synchronization (SNTP setting) can be tested in the main menu under
"Diagnostics -
> Simulation -> SNTP"
.
SNTP must be enabled beforehand in the main menu under
"Setup -> Advanced
setup -> System -> Date/time set-up -> SNTP"
.
Note: The test can take some time. A message is provided on the device once the test
has finished.
11.10.4 Relay test
The relay selected under
"Diagnostics -> Simulation -> Relay x"
can be switched
manually in the main menu.
11.11 Initialize modem
Initializes the modem connected (to automatically answer calls). The modem must support
the complete AT command syntax.
• Set the baud rate in the main menu under
"Setup -> Advanced setup ->
Communication -> Serial interface"
and select
"RS232"
as the interface type.
• Connect the modem to the RS232 interface of the device. For this purpose only use
the modem cable, which is available as an accessory.
A GSM modem can only be initialized if a SIM card is inserted and the PIN is entered
or the prompt to enter the PIN has been disabled.
11.12 Resetting the measuring device
The device can be reset to the as-delivered state with a PRESET. This function should only
be performed by a service technician.
The function can be found in the main menu under
"Expert -> System -> PRESET"
.
PRESET is only visible under "Expert" once the service code has been entered.
Procedure for resetting the measuring device
The PRESET returns all parameters to the factory default setup! The internal memory
content is deleted!
‣
Save the setup and measured values on the USB stick or SD card. Then perform a
PRESET.
The device is reset to the factory default settings.