Ecograph T, RSG35
Commissioning
Hauser
37
6. Once the device settings have been accepted, information to this effect is displayed in
the Web server
The function for saving the setup data must be enabled at the device for the Web
server under
"Setup -> Advanced setup -> Communication-> Ethernet -> Web
server settings; Setup -> Yes"
.
9.7
Simulation
Various functions/signals can be simulated for test purposes here.
NOTICE
Selecting simulation: Simulation of the relays and the WebDAV client can be found in
the main menu under "Diagnostics -> Simulation". The simulation of the measured
values can be found in the main menu under "Expert -> Diagnostics -> Simulation".
Only the simulated values are recorded during simulation. The simulation is recorded in
the event logbook.
‣
Do not start simulation if measured value recording must not be interrupted!
9.8
Protecting settings from unauthorized access
After configuration, the setup should be protected against unauthorized access. The
following options are available:
• Protection per control input
• Protection via release code
• Protection via user roles
In order to change any parameter, the correct code must first be entered or the device must
be unlocked using the control input.
Setup lock via control input:
The settings for the control input can be found in the main
menu under
"Setup -> Advanced setup -> Inputs -> Digital inputs -> Digital input X ->
Function: Control input; Action: Lock setup"
.
It is preferable to lock the setup using a control input.
Setting up an access code:
The settings for the access code can be found in the main
menu under
"Setup -> Advanced setup -> System -> Security -> Protected by -> Access
code"
. Factory setting: "open access", i.e. modifications can always be made.
Make a note of the code and store in a safe place.
Setting up user roles:
The settings for the user roles (operator, admin and service) are
provided in the main menu under
"Setup -> Advanced setup -> System -> Security ->
Protected by -> User roles"
. Factory setting: "open access", i.e. modifications can always
be made.
The passwords should be changed during commissioning.
Make a note of the code and store in a safe place.