Deltabar S PROFIBUS PA
Operation
Hauser
21
6.2.2 Function of the operating elements – on-site display not connected
Operating key(s)
Meaning
P02-xxxxxxxx-19-xx-xx-xx-107
– Position adjustment (zero point correction): Press key for at least 3 seconds. If the
LED on the electronic insert lights up briefly, the pressure applied has been
accepted for position adjustment.
See also Page 32 (Pressure measuring mode), Page 36 (Level measuring mode)
or Page 38 (Flow measuring mode).
– Total reset: Press key for at least 12 seconds. If the LED on the electronic insert
lights up briefly, the reset is being carried out.
P01-xxxxxxxx-19-xx-xx-xx-109
Set address in the bus.
See also Page 27, Section 4.4 "Configuring the device
address".
P01-xxxxxxxx-19-xx-xx-xx-108
– DIP-switch 1: for locking/unlocking measured-value-relevant parameters
Factory setting: off (unlocked)
– DIP switch 2: damping on/off
Factory setting: on (damping on)
0%
Zero
on
off
1 2 3 4 5 6 7 8
Address
2
1
CK
ON
3
4
5
6
7
8
S D A 0
8
0 1
SW
HW
1
2
on
off
τ