Electrical connection
19
7
Electrical connection
!
WARNING
If the operating voltage is > 35 VDC: Dangerous contact voltage at terminals.
Risk of electric shock!
►
In a wet environment, do not open the cover if voltage is present.
The sensor modules have a designation independent of the master/slave configuration. This
indicates where the sensor module is typically installed:
• Sensor module LP
LP = Low pressure; top
• Sensor module HP
HP = High pressure; bottom
For additional information, see "Function" (
7.1
Connecting the sensor mod. LP to the sensor mod. HP
!
WARNING
Is the supply voltage switched off?
Risk of electric shock and/or explosion!
►
Switch off the supply voltage before connecting the device.
• Screw on the housing cover of the terminal compartment of the sensor module LP.
• Guide the cable of the sensor module HP through the cable gland of the sensor module LP. Use
the shielded 4-wire cable that is provided. The wire ends are color-coded to match the
corresponding terminal.
• Connect device in accordance with the following diagrams.
• Screw down housing cover.
6
7
5
5
6
2
3
4
3
4
1
2
1
6
NPT ½"
M20
8
A0017528
1
BK (black)
2
BU (blue)
3
WH (white)
4
BN (brown)
5
Sensor module LP
6
Sensor module HP
7
Ground terminal
8
Torque 0.4 Nm