Description of parameters
Cerabar S 4 to 20mA HART
12
Hauser
P01-MIDxxxxx-19-xx-xx-EN-026
Fig. 5:
Function group POSITION ADJUSTMENT
SET LRV (245)
Entry
Set lower range value – without reference pressure.
Enter pressure value for the lower current value (4 mA).
Factory setting:
0.0 or as per order specifications
SET URV (246)
Entry
Set upper range value – without reference pressure.
Enter pressure value for the upper current value (20 mA).
Factory setting:
High sensor limit (
see PRESS. SENS HILIM, Page 28) or as per order specifications
DAMPING VALUE (247)
Entry
Enter damping time (time constant
).
The damping affects the speed at which all subsequent elements, such as the onsite
display, measured value and current output react to a change in the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 2: (GROUP SELECTION
) QUICK SETUP "Pressure"
Parameter name
Description
1)
1)
LANGUAGE
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
EXTENDED SETUP
CALIB. OFFSET
POS. INPUT VALUE
1) Display via
on-site display only
Table 3: (GROUP SELECTION
) OPERATING MENU
SETTINGS
POSITION ADJUSTMENT
Parameter name
Description
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the container is empty or
partially filled, the measured value does not display zero. Cerabar S provides two different options for carrying out
position adjustment.
Recommendation:
• The pressure difference between zero (set point) and the measured pressure need not be known.
– POS. INPUT VALUE
• The pressure difference between zero (set point) and the measured pressure is known.
– CALIB. OFFSET