Cerabar PMP51B Analog
Commissioning
Hauser
33
8.3.2
Linearization
In the following example, the volume in a tank with a conical outlet should be measured in
m
3
.
Prerequisites:
• Points for linearization table are known
• Level calibration is performed
• Linearization characteristic must continually increase or decrease
h
[m]
0
0
3.0
3.5
V
[m
3
]
V
[m ]
3
20
4
0
3.5
I
[mA]
A0038910
1. In the
Assign PV
parameter, the
Scaled variable
option must be configured
Menu path: Application → HART output → HART output → Assign PV
2. In the
Scaled variable unit
parameter, set the desired unit
Menu path: Application → Sensor → Scaled variable → Scaled variable unit
3. The linearization table can be opened via the
Go to linearization table
parameter
Table
option.
Menu path: Application → Sensor → Scaled variable → Scaled variable transfer
function
4. Enter the desired table values.
5. The table is activated once all the points in the table have been entered.
Result:
The measured value after linearization is displayed.
• Error message F435 "Linearization" and the alarm current appear as long as the
table is being entered and until the table is activated
• The 0% value (= 4 mA) is defined by the smallest point in the table
The 100% value (= 20 mA) is defined by the largest point in the table
• The assignment of the volume/mass values to the current values can be changed
with the
Lower range value output
parameter and
Upper range value output
parameter
8.4
Protecting settings from unauthorized access
8.4.1
Hardware locking or unlocking
DIP switch 1 on the electronic insert is used to lock or unlock operation.
If operation is locked via the DIP switch, the key symbol appears on the local display.