Safety function
Proline Prosonic Flow P 500 HART
14
Hauser
NOTICE
Use the measuring device according to the specifications.
‣
Pay attention to the medium properties and the environmental conditions.
‣
Carefully follow instructions pertaining to critical process situations and installation
conditions.
Detailed information on:
• Installation
• Electrical connection
• Medium properties
• Environment
• Process
Operating Instructions and Technical Information
Further information on the suitability of the measuring device for safety-related
operation is available from your Hauser sales center.
4.2.4
Information on measured errors
When the measured value is transmitted via the 4–20 mA current output, the measuring
device's relative measured error is made up of the contribution of the digitally determined
measured value and the accuracy of the analog current output. These contributions, which are
listed in the device documentation, apply under reference operating conditions and can
depend on the sensor version ordered.
The measured error of the digitally determined measured value comprises the measured error
of the measuring device and an additional, installation-specific measured error that is
independent of the measuring device.
The device's measured error is:
Nominal diameter
Measuring device error limits
[mm]
[in]
15
½
±0.5 % o.r. ± 5 mm/s (0.20 in/s)
25 to 200
1 to 8
±0.5 % o.r. ± 7.5 mm/s (0.30 in/s)
> 200
> 8
±0.5 % o.r. ± 3 mm/s (0.12 in/s)
For detailed information on the maximum measured error, see the Operating Instructions