ENDA ELC-186RT User Manual Download Page 1

ENDA

 

ELC-186RT

ENDA PLC PROGRAMMABLE LOGIC CONTROLOR
USER'S MANUAL

1) To avoid damaging the system, do not connect/disconnect the device when power 

is on.

2) Make wiring according to user manual to avoid damaging the system.
3) Do not touch live wires. 
4) Make sure the ground connection is wired. 

5) CE Market according to European Norms.

ELC-186RT PLC unit has got support 8 digital input, 2 relay output, 4 Transistor output.
I/O capacity can extend to 256 point with expansion modules.  

PLC parts and description

1

100Mb Ethernet port

10 Digital input terminal 

2

RS485 serial port

11 IO status LEDs

3

RS232 serial port

12 Digital output terminals

4

PLC power status LED

13 Label area

5

PLC error status LED

14 DIN Ray installation flange

6

Program RUN status LED 

15 Expansion modul BUS connector. 

7

Reset button

16

8

Power supply terminal

17

9

DIN Ray installation flange 

      Technical Specification

Name

Part

Description

General

Power supply

24VDC, ±15% tolerans

Power 
consumption

3WMax.

CPU process speed 80ns/command

Program language

Graphical Ladder diagram with EndaSoft software.

Program capasity

48kB (Complied code)

Commands

Logic, mathematical, communication, fast counter and timers, function  blocks processed.

Communication

ports

Ethernet port

100MB ethernet port for PC programming and network connections. Connection through 
the and programmable feature.

RS232

Serial port, MODBUS RTU protocol support

RS485

Serial port, MODBUS RTU protocol support 

Input/Output

Digital outputs

2 channels 220V 3A relay output, 4 channels pnp 24VDC transistor output, (QP2 and QP4 
are high speed output max 100kHz)

Digital inputs

8 channels 24VDC pnp, 5mA connection, Logic 1 for >14VDC, Logic 0 for < 13VDC 

Memory

Integer registers

1024 signed registers

Float registers

1024 signed float 32 registers

Counters

256 counters 32 bit up/down cunter

Timers

128 timer with 1ms resolution, 4 type timers

System registers

128 signed registers for accessing system properties

Environmental 

conditions

Temperature

-10..+60C (without icing)

Humidity

5..95rH nem 

Do not use the device in locations subject to corrosive or flammable gasses.

Please read this document carefully before using this products! The guarantee will be 
invalidated if the device is damaged by not following instructions detailed in the manual. 
The company shall not be responsible for any damage or losses however caused, which 
may be experienced as a result of the installation or use of this product.

TECHNICAL SPECIFICATIONS 