DEVICE CONFIGURATION
smart Econ - emz-HCW - 180116
139
Configure circulation temperatures
• Select ›MIN DHW-TEMP CIRC‹ in the ›DOMESTIC HOT WATER‹ menu.
• Change the ›limit value‹ if necessary.
Minimum storage tank temperature for release of circulation
(Factory settings: 38.0 °C, setting range: 0.0 - 95.0 °C)
“Change values” on page 23
• Select ›MAX RF TEMP CIRC‹ in the ›DOMESTIC HOT WATER‹ menu.
• Change the ›limit value‹ if necessary.
Maximum temperature in the return line of the circulation
Temperature is reached = circulation stops
(Factory settings: 38.0 °C, setting range: 0.0 - 85.0 °C)
“Change values” on page 23
If the temperature in the return line of the circulation is higher than the set limit value, the circulation
pump is switched off.(The circulation system is flushed.)
MIN DHW-TEMP CIRC
^
limit value
38.0
BACK
i
MAX RF-TEMP CIRC
^
limit value
38.0
BACK
i