DEVICE CONFIGURATION
smart Econ - emz-HCW - 180116
137
Configure domestic hot water priority
• Select ›DHW PRIORITY ON/OFF‹ in the ›DOMESTIC HOT WATER‹ menu.
• Change the ›limit value‹ if necessary.
1.0 = Priority active
0.0 = Priority disabled.
“Change values” on page 23
Configuring the domestic hot water pump
• Select ›SETTINGS PUMP DHW‹ from the ›DOMESTIC HOT WATER‹ menu.
• Change the parameters if necessary.
DHW PRIORITY ON/OFF
^
limit value
1.0
BACK
i
SETTINGS PUMP DHW
^
stop delay time (sec)
30
sw itch on delay (min)
0
BACK
i