DEVICE CONFIGURATION
smart Econ - emz-HCW - 180116
117
Configure solar system
(Only for systems with solar collector, depending on the selected system)
• Select ›SOLAR UNIT‹ in the ›COMMISSIONING‹ menu.
• Select ›SOLAR‹ in the ›SOLAR UNIT‹ menu.
• Change the parameters if necessary.
- ›hysteresis (K)‹: Switch-on hysteresis solar pump
Boost of the current collector temperature above the current buffer temperature to start the solar
pump
(Setting range: 0-99 K)
- ›storage max °C‹: Maximum permissible buffer temperature when solar pump is exceeded =
OFF
(Setting range: 0-99 K)
SOLAR UNIT
^
SOLAR
TANK COOLING
PUMP SETTINGS
SET COL. MIN TEMP
SET TEMP COLL.<>TANK
PUMP START SPEED
SOLAR PUMP MIN SPEED
SOLAR PUMP MAX SPEED
i
STOP TEMP COL COOLING
BACK
SOLAR
^
hysteresis (K)
8
storage max (°C)
80
sw itch on delay (min)
0
BACK
i