ULT-MVP

 

  Multi-Voltage Vehicle Loop Detector 

 

Instruction Manual 

 

The ULT-MVP vehicle loop detector allows for detection of metallic objects entering the field around an 
induction  loop.  This  detector  automatically  adjusts  from  12  VDC  up  to  240  VAC  which  eliminates  

the  installer’s  nee

d  to  match  available  power  to  an  appropriately  rated  vehicle  detector.  

The  ULTRA

METER™  display  feature  makes  set

-up  easy  by  displaying  the  optimum  sensitivity  setting 

required to detect a vehicle positioned near the loop. Ten sensitivity settings allow for fine adjustment  
of  the  detection  level.  The  ULT-MVP  provides  relay  contact  outputs  indicating  vehicle  presence  and  a 
second  set  of  relay  contact  outputs  providing  auxiliary  functions.  The  second  output  can  be  used  for  
loop  fault  or  pulse  on  entry/pulse  on  exit,  or  the  EMX  exclusive  feature,  Detect-on-Stop

™ 

(DOS

®

).  

The  ULT-MVP  features  automatic  sensitivity  boost  (ASB),  delay,  fail-safe/fail-secure  and  
infinite or normal (5 minute) presence. Four frequency settings provide flexibility in preventing crosstalk  
in multi-loop applications. 

 

Cautions and Warnings

 

 

This  product  is  an  accessory  or  part  of  a  system.    Install  the  ULT-MVP  according  to 
instructions  from  the  gate  or  door  operator  manufacturer.  Comply  with  all  applicable  
codes and safety regulations. 

  

 

Specifications 

 

 

 

 

Power 

12-60 VDC or 12-240 VAC (48-62 Hz) 

Operating Current (Standby/Detect) 

25 mA/50 mA 

Loop Frequency 

4 settings (low, med-low, med-hi, high) 

Loop Inductance 

20-

2000 µH (Q factor ≥ 5)

 

Surge Protection 

Loop circuitry protected by surge suppressors 

Presence Relay 

SPDT relay contacts (form C) 

Output B Relay 

SPDT relay contact (form C) 

Contact Rating (Resistive Load) 

2 A @ 30 VDC, 0.5 A @ 125 VAC 

Operating Temperature 

-40º to 82ºC (-40º to 180ºF) 0 to 95% relative humidity  

Environmental Rating 

IP30 

Connector 

11 pin male connector (JEDEC B11-88)  
compatible with DIN rail mount socket or wire harness 

Dimensions (L x W x H) 

73 mm (2.9”) x 38 mm (1.2”) x 78 mm (3.1”)

 

TM 

Summary of Contents for ULT-MVP

Page 1: ...e feature Detect on Stop DOS The ULT MVP features automatic sensitivity boost ASB delay fail safe fail secure and infinite or normal 5 minute presence Four frequency settings provide flexibility in pr...

Page 2: ...ntact rating 2A 30 VDC 0 5A 125 VAC Output B configurable for Pulse on Entry Pulse on Exit Detect On Stop or Loop Fault modes Description US DIN Rail Socket for ULT MVP U EU DIN Rail Socket for ULT MV...

Page 3: ...ashing 4 Power Loop Fault Indicator Green LED Normal Operation on Upon power up the detector initializes by automatically tuning to the loop The green LED indicates that the detector is powered and op...

Page 4: ...e for four possible modes In Pulse on Entry Exit mode Output B will be activated for approximately 500ms when a vehicle is entering or exiting the detection zone The Detect On Stop DOS feature require...

Page 5: ...ris from the finished cut with compressed air Place sand over the loop wire to the surface and pack tightly Lay new asphalt GRAVEL OR SOIL INSTALLATION While this is not a recommended installation for...

Page 6: ...loops and detectors are utilizing the same or very similar frequency configure DIP switches 7 and 8 on one of the devices For example Move one ULT MVP to the low frequency setting and the second ULT...

Page 7: ...ose connection Perform a megger test from loop lead to ground it should be more than 100 megaohms Check loop connections to terminals Verify splices are properly soldered and sealed against moisture O...