Version
5.0
Page 30 of 33
10
Maintenance
10.1
Turning off the Unit
Set the System to ‘OFF’ and Battery to ‘OFF’ and click ‘Apply Changes’. This will power down the inverter
and the charger but the system will remain powered on and communicating.
10.2
User Maintenance
1.
The user is not allowed to remove any covers on the Elektrobank 14, only a trained
professional is permitted to do this
2.
The Elektrobank 14 does not require scheduled maintenance and only requires an external
debris and salt clean, recommended every 6 months by the user.
3.
Check for signs of ingress by insects, animals, plants or water/dust. Check for any signs of
corrosion. Call your service technician if you see any signs.
4.
Then, with a dry cloth or soft brush, clean the whole product. Make sure all debris is cleared.
10.3
Trained Service Professional Maintenance
Scheduled maintenance by a service professional is not required.
If maintenance is required, always ensure the unit is completely de-powered and isolated before opening
the main door and before removing the internal escutcheon panel.
1.
Ensure grid voltage is isolated with an external locked off circuit breaker or isolator switch.
2.
Ensure backup voltage is isolated with a locked off circuit breaker or isolator switch.
3.
Ensure PV connectors are disconnected, or PV isolators are OFF and locked.
4.
Open the main door
5.
Ensure battery Circuit breaker, grid and backup circuit breakers are all in the OFF position.
6.
Ensure there is no LED light on the front of the unit