Troubleshooting and maintenance
Error display and remedying errors
Errors which cannot be recovered manually
* The failure contact does not function
Display
Error
Cause
Remedy
Program problem
External noise inter-
ference
Connect a parallel RC burst absorber
across the magnetizing coil of the mag-
netic contactor that causes interference
EEPROM problem Faulty EEPROM
Replace EEPROM
*
Voltage too high
during stop
Detection circuit mal-
function
Send the VSD back to be repaired
*
Voltage too low
during stop
1. Power voltage too
low
2. Restraining resis-
tor or fuse burnt out
3. Detection circuit
malfunction
1. Check if the power voltage was correct
or not
2. Replace the restraining resistor or the
fuse
3. Send the VSD back to be repaired
*
The VSD is over-
heated during
stop
1. Detection circuit
malfunctions
2. Ambient tempera-
ture too high or bad
ventilation
1. Send the VSD back to be repaired
2. Improve ventilation conditions
Current Sensor
detecting error
Current sensor error
or circuit malfunction
Send the VSD back to be repaired
CPF
EPR
-OV-
-LV-
-OH-
CTER
Summary of Contents for VSC 48-009
Page 1: ...Emotron VSC Variable Speed Drive Quick Setup Guide Multilingual...
Page 3: ...Emotron AB 01 3990 11r3...
Page 15: ...14 Anmerkungen zur Verkabelung Emotron AB 01 3990 11r3...
Page 38: ...Emotron AB 01 3990 11r3 Programmierungsanweisungen und Men liste 37...
Page 130: ...Emotron AB 01 3990 11r3 Localizaci n de aver as y mantenimiento 129...
Page 142: ...Emotron AB 01 3990 11r3 Kabelaansluitingen 141...
Page 163: ...162 Programmeringsinstructies en Menulijst Emotron AB 01 3990 11r3...
Page 182: ...Emotron AB 01 3990 11r3 Kabeldragning 181...
Page 209: ...208 Fels kning och underh ll Emotron AB 01 3990 11r3...