Emotron AB 01-3990-11r3
Wiring notes
49
Wiring notes
Fuse types
Drive input fuses are provided to disconnect the drive from power in the event
that a component fails in the drive’s power circuitry. The drive’s electronic pro-
tection circuitry is designed to clear drive output short circuits and ground
faults without blowing the drive input fuses. The table below shows the VSC
input fuse ratings.
To protect the VSD most effectively, use fuses with current-limiting function.
RK5, CC/T TYPE FUSE FOR VSC
Fuse ratings are based upon 500V for 460V VSDs
•
To avoid shock hazards, do not touch any electrical component when the
power is applied or until the power plug has been disconnected for five min-
utes. Other action should be performed after the change indicator goes off.
•
Do not wire the on the VSD while it is still electrified. Disregarding this
could cause serious injury or death.
This product is designed for use in Pollution Degree 2 environment or equiva-
lent environmentsenvironments or equivalent.
VSC 48- HP
KW
KVA
100% CONT
Output
AMPS (A)
Max.RK5
FUSE
Rating(A)
Max.CC or T
FUSE
Rating(A)
440V
class (3
φ
)
009
5
3.7
6.7
8.8
20
30
013
7.5
5.5
9.9
13
25
35
018
10
7.5
13.3
17.5
30
50
Summary of Contents for VSC 48-009
Page 1: ...Emotron VSC Variable Speed Drive Quick Setup Guide Multilingual...
Page 3: ...Emotron AB 01 3990 11r3...
Page 15: ...14 Anmerkungen zur Verkabelung Emotron AB 01 3990 11r3...
Page 38: ...Emotron AB 01 3990 11r3 Programmierungsanweisungen und Men liste 37...
Page 130: ...Emotron AB 01 3990 11r3 Localizaci n de aver as y mantenimiento 129...
Page 142: ...Emotron AB 01 3990 11r3 Kabelaansluitingen 141...
Page 163: ...162 Programmeringsinstructies en Menulijst Emotron AB 01 3990 11r3...
Page 182: ...Emotron AB 01 3990 11r3 Kabeldragning 181...
Page 209: ...208 Fels kning och underh ll Emotron AB 01 3990 11r3...