CG Drives & Automation 01-7491-01r0
Troubleshooting, Diagnoses and Maintenance
193
12.
Troubleshooting, Diagnoses and Maintenance
12.1 Trips, warnings and limits
In order to protect the AC drive the principal operating
variables are continuously monitored by the system. If one
of these variables exceeds the safety limit an error/warning
message is displayed. In order to avoid any possibly
dangerous situations, the inverter sets itself into a stop Mode
called Trip and the cause of the trip is shown in the display.
Trips will always stop the AC drive. Trips can be divided into
normal and soft trips, depending on the setup Trip Type, see
menu “[250] Autoreset”. Normal trips are default. For
normal trips the AC drive stops immediately, i.e. the motor
coasts naturally to a standstill. For soft trips the AC drive
stops by ramping down the speed, i.e. the motor decelerates
to a standstill.
“Normal Trip”
•
The AC drive stops immediately, the motor coasts to a
standstill.
•
The Trip relay or output is active (if selected).
•
The Trip LED is on.
•
The accompanying trip message is displayed.
•
The “TRP” status indication is displayed (area D of the
display).
•
After reset command, the trip message will disappear and
menu [100] will be indicated.
“Soft Trip”
•
the AC drive stops by decelerating to a standstill.
During the deceleration.
•
The accompanying trip message is displayed, including
an additional soft trip indicator “S” before the trip time.
•
The Trip LED is flashing.
•
The Warning relay or output is active (if selected).
After standstill is reached.
•
The Trip LED is on.
•
The Trip relay or output is active (if selected).
•
The “TRP” status indication is displayed (area D of the
display).
•
After reset command, the trip message will disappear and
menu [100] will be indicated.
Apart from the TRIP indicators there are two more
indicators to show that the inverter is in an “abnormal”
situation.
“Warning”
•
The inverter is close to a trip limit.
•
The Warning relay or output is active (if selected).
•
The Trip LED is flashing.
•
The accompanying warning message is displayed in
window “[722] Warning”.
•
One of the warning indications is displayed (area F of
the display).
“Limits”
•
The inverter is limiting torque and/or frequency to avoid
a trip.
•
The Limit relay or output is active (if selected).
•
The Trip LED is flashing.
•
One of the Limit status indications is displayed (area D
of the display).
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......