CG Drives & Automation 01-7491-01r0
157
11.5.2
Submenu with all the settings for the digital inputs.
To select the function of the digital input.
On the standard control board there are eight digital inputs.
If the same function is programmed for more than one input
that function will be activated according to “OR” logic if
nothing else is stated.
NOTE: Additional inputs will become available when
the I/O option boards are connected.
521
DigIn 1
Default:
RunL
Off
0
The input is not active.
Ext. Trip
3
Be aware that if there is nothing
connected to the input, the AC drive will
trip at “External trip” immediately.
NOTE: The External Trip is active low.
NOTE: Activated according to “AND”
logic.
Stop
4
Stop command according to the selected
Stop mode in menu [33B].
NOTE: The Stop command is active low.
NOTE: Activated according to “AND”
logic.
Enable
5
Enable command. General start condition
to run the AC drive. If made low during
running the output of the AC drive is cut
off immediately, causing the motor to
coast to zero speed.
NOTE: If none of the digital inputs are
programmed to “Enable”, the internal
enable signal is active.
NOTE: Activated according to “AND”
logic.
RunR
6
Run Right command (positive speed). The
output of the AC drive will be a
clockwise rotary field.
RunL
7
Run Left command (negative speed). The
output of the AC drive will be a
counter-clockwise rotary field.
Reset 9
Reset command. To reset a Trip condition
and to enable the Autoreset function.
Preset Ctrl1 10 To select the Preset Reference.
Preset Ctrl2 11 To select the Preset Reference.
Preset Ctrl3 12 To select the Preset Reference.
MotPot Up 13
Increases the internal reference value
according to the set Acc MotPot time
[333]. Has the same function as a “real”
motor potentiometer, see fig. 114.
MotPot
Down
14
Decreases the internal reference value
according to the set Dec MotPot time
[334]. See MotPot Up.
Pump 1
Feedb
15
Feedback input pump1 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump 2
Feedb
16
Feedback input pump 2 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump 3
Feedb
17
Feedback input pump3 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump 4
Feedb
18
Feedback input pump 4 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump 5
Feedb
19
Feedback input pump5 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Pump 6
Feedb
20
Feedback input pump 6 for Pump/Fan
control and informs about the status of the
auxiliary connected pump/fan.
Set Ctrl 1
23
Activates other parameter set. See table
36 for selection possibilities.
Set Ctrl 2
24
Activates other parameter set. See table
36 for selection possibilities.
Mot
PreMag
25
Pre-magnetises the motor. Used for faster
motor start.
Jog 26
To activate the Jog function. Gives a Run
command with the set Jog speed and
Direction, page 133.
Ext Mot
Temp
27
Be aware that if there is nothing
connected to the input, the AC drive will
trip at
“External Motor Temp” immediately.
NOTE: The External Motor Temp is active
low.
Loc/Rem
28
Activate local mode defined in [2171] and
[2172].
AnIn select 29
Activate/deactivate analogue inputs
defined in [513A], [516A], [519A] and
[51CA]
LC Level
30
Liquid cooling low level signal.
NOTE: The Liquid Cooling Level is active
low.
Brk Ackn
31
Brake acknowledge input for Brake Fault
control. Function is activated via this
selection see menu [33H] page 130.
Sleep
32
Possible to enter sleep mode through
DigIn.
Timer 1
34
Timer 1 will be activated on the rising edge
of this signal.
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......