116
Functional description
CG Drives & Automation 01-7491-01r0
Main menu for communication fault/warning settings. For
further details please see the Fieldbus option manual.
Menus [2641] and [2642] are specifically used for Fieldbus
option mounted on interface X4.
Menus [2643] and [2644] are specifically used for integrated
RS485 interface on X1: A+ and B-.
Communication Fault Mode [2641]
Selects action if a Fieldbus fault is detected.
Communication Fault Time [2642]
Defines the delay time for the Fieldbus trip/warning.
Selects action for timeout on integrated RS485 interface on
X1: A+ and B-.
Defines the delay time for the integrated RS485 trip/
warning.
Keybord Communication Fault Mode
[2645]
When keyboard is removed in drive running condition and
"[214] Ref Control" or "[215] Run/Stp Ctrl" is set to
"Keyboard" the drive should come to stop.
Keyboard Communication Fault Time
[2646]
Defines the delay time for detection of a removed control
panel provided that 2645 is either trip or warning.
Communication fault for control
panel port
This feature enables communication fault for external
controlling equipment connected to the CP port. Most
importantly this enables detection if a wireless connection,
via BLE or WiFi CP, is disconnected.
Fault is only enabled if all of following conditions are met:
•
"[214] Ref Control" or "[215] Run/Stp Ctrl" is set to
"Com".
•
A device connected to the CP port has written to any of
the communication command registers:
- Run (2 or 42902)
- RunR (3 or 42903)
- RunL (4 or 42904)
- Reference (42905)
2641
ComFlt Mode
Default:
Off
Off
0
No communication supervision.
Trip
1
Fieldbus selected:
The AC drive will trip if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
Warning
2
Fieldbus selected:
The AC drive will give a warning if:
1. The internal communication between
the control board and fieldbus option is
lost for time set in parameter [2642].
2. If a serious network error has occurred.
NOTE: Menu [214] and/or [215] must be set to COM
to activate the communication fault function.
2642
ComFlt Time
Default:
0.5 s
Range:
0.1-15 s
2643
485Flt Mode
Default:
Off
Off
0
No communication supervision.
Trip
1
The AC drive will trip if there is no
communication for time set in parameter
[2644].
Warning
2
The AC drive will give a warning if there is
no communication for time set in
parameter [2644].
NOTE: Menu [214] and/or [215] must be set to COM
to activate the communication fault function.
2644
485Flt Time
Default:
0.5 s
Range:
0.1-15 s
2645
KbdComFMode
Default:
Trip
Off
0
No supervison of keybord.
Trip
1
The drive will trip after time set in
parameter [2646] if keyboard/control
board is removed.
Warning
2
The drive will give a warning after time
set in parameter [2646] if the
keyboard/control board is removed.
2646
KbdComFTime
Default:
2 s
Range:
0.1 s - 15 s
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......